The unit is rated for a -5 to 40 °C operating range, with a permissible 80 °C return-line temperature, so process return temperatures above 40 °C are only acceptable up to 80 °C.
Defines the maximum allowable return temperature when selecting the chiller for a process loop.
Source
“Permissible temperature in return line 80 °C”
Selection
Cooling capacity is 0.28 kW at 15 °C and 0.2 kW at 0 °C, so the chiller is only suitable for low-heat-load applications.
Allows the engineer to verify the chiller can remove the process heat load at the required temperature.
Source
“at 15°C 0,28 kW at 0°C 0,2 kW”
Selection
The refrigerant is R-290 (A3, H220) with a GWP of 0.02 and a charge of 0.041 kg, which affects flammable-refrigerant handling and environmental compliance.
A3 flammability classification requires awareness of ignition sources and ventilation during installation.
Source
“R-290 (A3, H220)”
Installation
The unit requires a 220-240 V single/two-phase 50/60 Hz supply with a minimum 10 A and maximum 16 A fuse, so the electrical supply must be sized accordingly.
Determines the electrical connection and protective device rating at the installation site.
Source
“220-240V 1~/2~ 50/60Hz”
Installation
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and combining -5% voltage with +2% frequency is not allowed.
Prevents installation on a supply where combined voltage and frequency deviations exceed the permitted envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The degree of protection is IP20, so the unit must be installed in a dry, protected environment away from water ingress.
Restricts installation locations to indoor, non-wet environments.
Source
“Degree of Protection IP20”
Installation
Ambient temperature must stay between 5 °C and 40 °C, and cooling capacity may drop if ambient temperature rises.
Requires the installation room to be kept within the ambient limits to preserve rated performance.
Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation
The pump connection is M16x1 male, and included accessories are a NW12 hose connector and M16x1 sleeve nuts, so hoses must match this thread.
Ensures the correct hose fittings are ordered and the circuit can be connected leak-free.
Source
“Pump connection M16x1 male”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used as heat transfer fluid.
Prevents chemical attack and pump failure when selecting the heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Guides the correct water/glycol mixture to avoid freezing at low operating temperatures.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Operation
The minimum filling capacity is 1.4 l and the expansion tank is 2 l, so the external loop volume must be considered when filling.
Ensures sufficient heat transfer fluid volume and expansion space for safe operation.
Source
“min. filling capacity 1,4 l”
Operation
The pump delivers up to 14 l/min at 0.25 bar pressure and 10.5 l/min suction at 0.17 bar, which limits the achievable external circuit flow.
Allows verification that the pump can overcome the pressure drop of the external circuit.
Source
“max. delivery 14 l/min”
Safety
The unit has safety classification I / NFL according to DIN 12876, which defines its suitability for flammable liquids.
Determines whether the chiller may be used with flammable heat transfer fluids under DIN 12876.
Source
“Safety classification I / NFL”
Compliance
The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011, so it is intended for industrial environments.
Class A equipment may cause radio interference and is not intended for residential use.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”