Induztr
Engineering Digest Document Viewer Related Models

Minichiller 800 OLÉ Technical Data

Contents

  1. Overview p. 1
    Product name and model identification on cover page
  2. Spec p. 2
    Technical data per DIN 12876 in tabular form
  3. p. 2 table, 6 rows

Technical data according to DIN 12876

CharacteristicValue
max. Fuse16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S622395

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit uses flammable R-290 refrigerant (A3, H220), so the installation site must be assessed for flammable-refrigerant requirements.

Refrigerant safety class A3 affects site selection, ventilation and compliance approvals.

Source
“R-290 (A3, H220)”
Selection

Cooling capacity is only 0.3 kW at -20 °C, so the chiller must be sized against the actual load at the lowest required temperature.

Capacity drops strongly with temperature and determines whether the unit can hold the process setpoint.

Source
“at -20°C 0,3 kW”
Installation

The chiller is air-cooled with a natural-draft refrigerant circuit, so adequate air flow and space around the unit are required.

Poor ventilation reduces cooling capacity and can trip the refrigeration machine.

Source
“air-cooled, natural”
Installation

The electrical supply must be 208-240 V single or two-phase at 50/60 Hz with a minimum 10 A fuse.

Confirms the available power feed and breaker rating before installation.

Source
“208-240V 1~/2~ 50/60Hz”
Installation

Voltage and frequency tolerances are ±5 % and ±2 % but may not be combined in the unfavorable direction.

Prevents motor and pump damage from out-of-tolerance supply combinations.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

The plastic pump is not resistant to acetone or polyglycols, so these fluids must not be used as heat transfer media.

Wrong fluid choice destroys the pump and contaminates the circuit.

Source
“The plastic pump is not resistant against acetone and polyglycols”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than used pure.

Prevents freezing and damage in the evaporator at sub-zero setpoints.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Operation

The return-line temperature may reach 80 °C even though the operating range is stated as -20...40 (80) °C.

Defines the maximum heat load temperature the unit can accept without damage.

Source
“Permissible temperature in return line 80 °C”
Installation

Ambient temperature must stay between 5 °C and 40 °C, and cooling capacity falls as ambient rises.

Room conditions directly affect achievable performance and must be checked at the site.

Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation

The pump connections are M16x1 male, and hose connector NW12 plus sleeve nuts are included.

Determines the hose adapters and fittings needed for the external circuit.

Source
“Pump connection M16x1 male”
Operation

Whisper mode reduces sound to 51 dB(A) but also reduces pump delivery to 14 l/min at 0.2 bar.

Quiet operation trades off hydraulic performance, which matters for loop pressure drop.

Source
“Delivery rate: 14 l/min”
Compliance

The equipment is classified Class A, Group 1 for electromagnetic disturbance under EN55011.

Class A equipment is intended for industrial environments and may need EMC measures in residential areas.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Three-phase devices below 63 A are supplied with cable but without a plug.

The installer must provide the appropriate plug and connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Maintenance

The minimum filling capacity is 2.8 l and the expansion tank is 2.2 l, so the external loop volume must be considered.

Ensures enough heat transfer fluid and expansion volume for safe operation.

Source
“min. filling capacity 2,8 l”