Unichiller 055Tw-H Technical Data Sheet

Contents

  1. Overview p. 1
    Product name and general description of the chiller unit
  2. Spec p. 2
    Technical data according to DIN 12876 standard
  3. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Operating temperature range-10...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C5,5 kW
Cooling power at 0°C3 kW
Cooling power at -10°C1,5 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity0,95 kg
CO2 equivalent1,3 t
Circulation pumpC3
max. delivery100 l/min
max. delivery pressure5,6 bar
Delivery at 0,3 bar97 l/min
Delivery at 1,0 bar90 l/min
Delivery at 1,5 bar84 l/min
Delivery at 2,0 bar77 l/min
Delivery at 2,5 bar71 l/min
Delivery at 3,0 bar64 l/min
Delivery at 3,5 bar57 l/min
Delivery at 4,0 bar48 l/min
Delivery at 4,5 bar39 l/min
Delivery at 5,0 bar27 l/min
Delivery at 5,5 bar8 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C330 l/h

Order-No.: 3015.0079.01; Unichiller 055Tw-H

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a differential pressure of at least 0.6 bar and no more than 6 bar.

The site cooling water system must be able to deliver this pressure window, otherwise the unit will not operate correctly or may be damaged.

Source
“min. cooling water differential pressure 0,6 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake temperatures between 5 °C and 20 °C, and pipes must be insulated if the water can fall below the condensation point.

Cooling water outside this range changes cooling capacity and can cause condensation, so the facility water supply must be checked before installation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.

The published cooling capacities are only valid at 15 °C cooling water, so the actual duty must be derated if the site water is warmer.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Water quality and treatment must be compatible with these materials to avoid corrosion or fouling of the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

The three-phase unit is supplied with a cable but without a plug, so the customer must provide a suitable connection.

The electrical installation must include a suitable 3-phase plug or isolator, since none is supplied with the unit.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but a -5 % voltage combined with a +2 % frequency is not allowed.

The site power quality must be checked against this combined tolerance rule, not just against each tolerance separately.

Source
“-5% voltage and +2% frequency -> not allowed!”
Compliance

The unit is EMC classified as Class A, Group 1 to EN55011, which is intended for industrial environments.

Class A equipment may cause interference in residential areas, so installation location and EMC environment must be considered.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety

The refrigerant is R-449A, classified A1 with GHS hazard H280, and the charge is 0.95 kg with a CO2 equivalent of 1.3 t.

Refrigerant safety class, hazard labelling and CO2 equivalent affect handling, leak detection and F-gas reporting obligations.

Source
“R-449A (A1, H280)”
Operation

The unit has adjustable overtemperature protection according to DIN 12876 and safety classification III / FL.

The overtemperature cut-out must be set correctly for the application to protect the process and the equipment.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection

The circulation pump delivers 100 l/min maximum, but flow falls to 8 l/min at 5.5 bar, so the system pressure drop must be matched to the pump curve.

External circuit pressure drop determines the actual flow, so the pump curve must be checked against the application resistance.

Source
“max. delivery 100 l/min max. delivery pressure 5,6 bar”
Installation

The unit requires a minimum filling capacity of 5.9 l and has an expansion volume of 7.5 l.

The external circuit volume and expansion vessel sizing must be checked to ensure proper filling and expansion allowance.

Source
“min. filling capacity 5,9 l Volume of expansion 7,5 l”
Installation

The unit has degree of protection IP20 and must be operated at ambient temperatures between 5 °C and 40 °C.

The installation room must be dry and within the ambient temperature range, since IP20 offers no water protection.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection

The unit is intended for externally closed applications and has a stainless steel circulation pump.

The application must be a closed external circuit; open or pressure-less systems are not suitable for this chiller.

Source
“For externally closed applications.”