Selection
The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines the application window and excludes processes requiring lower or higher temperatures.
Source
“Operating temperature range
-20...40 °C”
Performance
Cooling capacity drops from 6 kW at 15 °C to 1.4 kW at -20 °C, so capacity must be checked at the actual working temperature.
Sizing on nominal capacity alone risks insufficient cooling at low set points.
Source
“at 15°C
6 kW
at 0°C
5 kW
at -10°C
2,8 kW
at -20°C
1,4 kW”
Installation
The unit requires a 400 V 3-phase 50 Hz supply with 10 A max current and 3x16 A fusing.
Electrical infrastructure and protection must be planned accordingly before installation.
Source
“Power supply (3 Phase)
400V 3~ 50Hz
max. current (3 Phase)
10 A”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site.
Prevents delays at commissioning due to missing power connection hardware.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances are ±5% and ±2% but must not be combined in the unfavorable direction.
Site power quality must be verified to avoid invalid supply conditions and equipment damage.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The chiller is air-cooled, so sufficient ambient air and space for heat rejection must be ensured.
Air-cooled units need adequate ventilation and clearance to maintain cooling performance.
Source
“Refrigeration machine
air-cooled, CFC- and
HCFC-free”
Operation
Cooling capacity is valid at 20 °C room temperature and may drop if ambient temperature rises.
Performance must be derated in warm rooms to avoid undersized cooling.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Operation
The unit may only be operated between 5 °C and 40 °C ambient temperature.
Ambient conditions outside this range can impair operation and must be controlled.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280 and has a GWP of 1397.
Refrigerant handling, labeling and environmental obligations depend on this classification.
Source
“R-449A (A1, H280)”
Compliance
The CO2 equivalent of the refrigerant charge is 3.1 t, which triggers F-gas documentation and leak-check obligations.
Determines regulatory maintenance and reporting requirements for the refrigerant circuit.
Source
“CO2 equivalent
3,1 t”
Installation
The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.
Ensures correct hydraulic connection and avoids leaks or adapters.
Source
“Pump connection
G1 1/4 male”
Operation
The circulation pump delivers 80 l/min max at 5.6 bar max, with flow falling as pressure rises.
Hydraulic design must respect the pump curve to avoid insufficient flow in the loop.
Source
“max. delivery
80 l/min
max. delivery pressure
5,6 bar”
Installation
The unit has IP20 protection, so it must be installed in a dry, protected environment.
Prevents installation in wet or dusty locations that would violate protection rating.
Source
“Degree of Protection
IP20”
Compliance
The equipment is EMC class A group 1, which may require additional measures in residential environments.
Class A equipment is intended for industrial use and may cause interference in residential areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”