  1. Overview p. 1
    Introduces the Unichiller 060Tw-H chiller and its main features
  2. Spec pp. 1-2
    Performance, temperature range, and operating data per DIN 12876
  3. Spec p. 2
    Physical dimensions, weight, and process connection details
  4. p. 2 table, 15 rows
  5. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Consumption at water 15°C, flow -20°C380 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity5,9 l
Volume of expansion7,5 l
Overall dimensions WxDxH **600x600x1450 mm
Net weight210 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)13 A
Fuse (3 phase)3x16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S425010

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 060Tw-H (Order-No. 3026.0119.01)

ParameterValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C6 kW
Cooling power at 0°C5 kW
Cooling power at -10°C3,1 kW
Cooling power at -20°C1,7 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,15 kg
CO2 equivalent1,6 t
Circulation pumpC3
max. delivery80 l/min
max. delivery pressure5,6 bar
Delivery at 0,35 bar79 l/min
Delivery at 0,5 bar76 l/min
Delivery at 1,0 bar71 l/min
Delivery at 1,5 bar66 l/min
Delivery at 2,0 bar61 l/min
Delivery at 3,0 bar49 l/min
Delivery at 4,0 bar35 l/min
Delivery at 5,0 bar16 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C870 l/h
Consumption at water 15°C, flow 0°C730 l/h
Consumption at water 15°C, flow -10°C580 l/h

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a differential pressure between 1 and 6 bar.

Determines whether the site's cooling water loop can supply adequate pressure without overpressurizing the unit.

Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake between 5°C and 20°C, and pipes must be insulated if water temperature can fall below the condensation point.

Cooling water outside this range will degrade performance or cause condensation, affecting installation design.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.

Engineers must size the cooling water supply for worst-case water temperature, not just nominal conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Water chemistry must be checked to avoid corrosion or degradation of these wetted materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

Three-phase devices with current consumption below 63 A are delivered with a cable but without a plug.

The installer must provide and fit a suitable plug or hard-wire the supply, which affects electrical installation planning.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Compliance

Voltage tolerance is ±5% only when frequency tolerance is simultaneously ±2%, and certain combinations are not allowed.

Supply quality must be verified against these limits to avoid invalidating operation or damaging the unit.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety

The unit has safety classification III / FL according to DIN 12876 and adjustable overtemperature protection.

Confirms the built-in safety concept and that overtemperature protection must be configured for the application.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection

The refrigerant is R-449A with GWP 1397 and a CO2 equivalent of 1.6 t, which matters for environmental and regulatory reporting.

Refrigerant charge and GWP affect compliance obligations and environmental impact assessment during selection.

Source
“Global Warming Potential (GWP) 1397”
Operation

The unit is intended for externally closed applications and has an atmospheric open expansion tank.

The external circuit must be closed; open-loop or unsealed external circuits are not suitable.

Source
“For externally closed applications.”
Installation

The unit has protection degree IP20 and must be operated within an ambient temperature of 5°C to 40°C.

Site ambient conditions and ingress protection must match the installation location.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection

The pump connection is G1 1/4 male and the cooling water connection is G1/2 male.

Thread sizes determine the hoses and fittings needed for installation.

Source
“Pump connection G1 1/4 male Cooling water connection G1/2 male”
Performance

Cooling power is 6 kW at 15°C, 5 kW at 0°C, 3.1 kW at -10°C and 1.7 kW at -20°C.

Cooling capacity at the actual process temperature must be checked against the heat load.

Source
“at 15°C 6 kW at 0°C 5 kW at -10°C 3,1 kW at -20°C 1,7 kW”
Installation

The unit requires a 400 V 3~ 50 Hz supply with a 3x16 A fuse and maximum current of 13 A.

Electrical supply, protection and cabling must be sized accordingly.

Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current (3 Phase) 13 A Fuse (3 phase) 3x16A”