Unichiller 070T Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller 070T chiller unit and its main features
  2. Spec pp. 1-2
    Lists performance, temperature, and dimensional data per DIN 12876
  3. p. 2 table, 2 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
max. ambient temperature40 °C
from Serial-No.:1.0/19

Technical data according to DIN 12876 — Unichiller 070T (Order-No.: 3016.0025.01)

CharacteristicValue
Operating temperature range-10...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
Temperature stability at -10°C0,5 K
Safety classificationI / NFL
Cooling power at 15°C7 kW
Cooling power at 0°C4 kW
Cooling power at -10°C2,3 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Circulation pump:C3
max. delivery97 l/min
max. delivery pressure6,4 bar
Delivery at 0,35 bar93 l/min
Delivery at 0,5 bar92 l/min
Delivery at 1,0 bar86 l/min
Delivery at 1,5 bar82 l/min
Delivery at 2,0 bar77 l/min
Delivery at 3,0 bar65 l/min
Delivery at 4,0 bar53 l/min
Delivery at 5,0 bar39 l/min
Delivery at 6,0 bar17 l/min
Pump connectionG1 1/4 male
min. filling capacity5 l
Volume of expansion7,5 l
Overall dimensions WxDxH **600x790x1614 mm
Net weight234 kg
Power supply (3 Phase)460V 3~ 60Hz
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C

** — сноска в исходном тексте не раскрыта.

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -10 to 40 °C, so it must be selected only for applications within this window.

Defines the process temperature envelope the unit can support.

Source
“Operating temperature range -10...40 °C”
Performance

Cooling capacity drops from 7 kW at 15 °C to 2.3 kW at -10 °C, so sizing must use the capacity at the actual lowest operating temperature.

Prevents undersizing when the process requires low-temperature operation.

Source
“Cooling power at 15°C 7 kW at 0°C 4 kW at -10°C 2,3 kW”
Installation

The unit requires a 460 V three-phase 60 Hz supply, so site power must match this configuration.

Electrical supply mismatch will prevent commissioning.

Source
“Power supply (3 Phase) 460V 3~ 60Hz”
Installation

External branch circuit protection according to UL 489 is required, so the installer must provide suitable upstream protection.

Necessary for compliant and safe electrical installation.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices below 63 A are supplied with cable but without a plug, so the site must provide a suitable connection.

Affects electrical installation planning and hardware procurement.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

Cooling capacity is valid at 20 °C room temperature and may drop at higher ambient temperatures, so ambient conditions must be considered.

Prevents performance shortfall in warm plant rooms.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit has IP20 protection, so it must be installed in a dry indoor environment protected from water and dust ingress.

Determines suitable installation location and environmental protection.

Source
“Degree of Protection IP20”
Operation

The minimum ambient temperature is 5 °C, so the installation site must not fall below this value.

Low ambient can affect operation and must be checked for outdoor or cold-room siting.

Source
“min. ambient temperature 5 °C”
Installation

The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.

Ensures correct hydraulic connection hardware.

Source
“Pump connection G1 1/4 male”
Selection

The minimum filling capacity is 5 l and expansion volume is 7.5 l, so the external loop volume must be compatible with the expansion tank.

Prevents overflow or insufficient fill in externally closed applications.

Source
“min. filling capacity 5 l Volume of expansion 7,5 l”
Safety

The refrigerant is R-449A with GHS classification H280 and GWP 1397, so refrigerant handling and environmental reporting must account for this.

Relevant for safety, leak response, and greenhouse gas reporting.

Source
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280) Global Warming Potential (GWP) 1397”
Compliance

The equipment is Class A Group 1 under EN55011, so it may cause radio interference in residential environments and EMI measures may be needed.

Affects installation in sensitive or residential electromagnetic environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Voltage and frequency tolerances are ±5% and ±2% respectively but not simultaneously in the disallowed combination, so supply quality must be verified.

Prevents operation outside permissible supply conditions.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Selection

The unit is intended for externally closed applications, so it should not be applied to open-loop or vented processes.

Defines the hydraulic application type the chiller is designed for.

Source
“For externally closed applications.”