Installation
The chiller requires a three-phase 400 V supply with a 3x10 A fuse, so the electrical installation must be sized accordingly.
Determines the site power supply, cable and protection device required before installation.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is water-cooled and needs a cooling water supply with at least 0.5 bar differential pressure and no more than 6 bar.
Cooling water pressure must be verified on site to ensure sufficient flow and avoid overpressure damage.
Source
“min. cooling water differential pressure 0,5 bar”
Installation
Cooling water inlet temperature must be kept between 5 °C and 20 °C, and pipes must be insulated if condensation can occur.
Out-of-range cooling water temperature reduces cooling capacity and can cause condensation and corrosion.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling capacity drops significantly as the required process temperature decreases, from 10 kW at +20 °C to 3.9 kW at -20 °C.
The chiller must be selected against the actual cooling load at the lowest required process temperature.
Source
“Cooling power at ambient temperature +20°C”
Performance
The circulation pump delivers 48 l/min maximum and its flow falls as pressure rises, reaching only 11 l/min at 3.0 bar.
External circuit pressure drop must be checked to confirm the pump can provide the required flow.
Source
“max. delivery 48 l/min”
Installation
The pump connection is G1 1/4 male and the cooling water connection is G1/2 male, so matching hoses and couplings are needed.
Ensures correct fittings and hoses are ordered and available for mechanical installation.
Source
“Pump connection G1 1/4 male”
Operation
The unit is rated IP20 and must be operated in ambient temperatures between 5 °C and 40 °C.
Installation location must provide adequate ventilation and avoid high ambient temperatures that reduce performance.
Source
“max. ambient temperature 40 °C”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and leak procedures must account for a pressurized gas hazard.
Affects site safety documentation, leak detection and service procedures for the refrigeration circuit.
Source
“R-449A (A1, H280)”
Compliance
The unit is classified as pressure equipment under Article 4.3 PED, which affects documentation and conformity requirements.
Needed for regulatory compliance and acceptance of the equipment on site.
Source
“Pressure equipment category Art. 4.3 PED”
Installation
Three-phase devices below 63 A are supplied with a cable but without a plug, so a suitable plug must be provided on site.
Prevents delays at commissioning because the electrical contractor must supply and fit the plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation
Voltage and frequency tolerances are ±5 % and ±2 % respectively, but not all combinations are allowed.
Site power quality must be checked to avoid invalid supply combinations and equipment malfunction.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Water quality and treatment must be selected to prevent corrosion and fouling of these materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
The unit weighs 274 kg and measures 740x1160x1050 mm, so floor loading and access routes must be planned.
Needed for rigging, transport route and installation space planning.
Source
“Overall dimensions WxDxH ** 740x1160x1050 mm”