Product introduction and general description of the chiller
Specp. 2
Technical data according to DIN 12876 standard
p. 1table, 27 rows
Unichiller GL 050w — Technical data according to DIN 12876
Parameter
Value
Order-No.
5505.0003.01
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 20°C
5 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
max. delivery
50 l/min
max. delivery pressure
3,5 bar
Pump connection
G1 1/4 male
Cooling water connection
G1/2 male
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
Volume of expansion
9,5 l
Overall dimensions WxDxH **
550x760x1455 mm
Power supply (3 Phase)
460V 3~ 60Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.
1.0/26
** Technical details and dimensions are subject to change. No liability is accepted for errors or omissions. Illustrations can deviate from the original.
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller requires cooling water with a differential pressure of at least 1 bar and no more than 6 bar at the connection.
Ensures the cooling water supply is adequate and within the unit's pressure limits to avoid poor performance or damage.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit is water-cooled and must be connected to a cooling water circuit with G1/2 male connections.
Determines the piping and fittings needed for installation.
Source
“Cooling water connection G1/2 male”
Operation
The cooling water inlet temperature must be between 5°C and 20°C; lower temperatures require insulation of the cooling water pipes.
Operating outside this range can cause condensation or reduced cooling performance.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.
Helps in sizing the cooling water supply and predicting performance under different conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the cooling water must be compatible.
Prevents corrosion or damage by ensuring suitable water quality.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance
Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but combinations like -5% voltage and +2% frequency are not allowed.
Ensures the power supply meets the unit's requirements and avoids invalid tolerance combinations.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
External branch circuit protection according to UL 489 is required.
Mandatory for electrical safety and compliance in the installation.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices with current consumption less than 63A are supplied with a cable but without a plug.
The installer must provide a suitable plug or hardwire connection.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The refrigerant is R-744 (CO2) with GHS hazard H280 (contains gas under pressure).
Requires awareness of pressure hazards and proper handling during installation and maintenance.
Source
“R-744 (A1, H280)”
Selection
The unit has a maximum delivery pressure of 3.5 bar and a maximum flow of 50 l/min.
Important for selecting external circuit components and ensuring they can withstand the pressure.
Source
“max. delivery pressure 3,5 bar”
Operation
The ambient temperature must be between 5°C and 40°C for proper operation.
Ensures the installation location meets the environmental conditions.
Source
“min. ambient temperature 5 °C”
Compliance
The equipment is compliant with US-SNAP and all applicable EU laws, with US-SNAP end-use for industrial process refrigeration.
Confirms regulatory compliance for the intended application.
Source
“This equipment is compliant to US-SNAP and all applicable EU laws.”