Performance, temperature, and technical data per DIN 12876
p. 2table, 3 rows
p. 1table, 34 rows
Technical data according to DIN 12876
Parameter
Value
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/26
Unichiller GL 1650w — Technical data according to DIN 12876
Parameter
Value
Order-No.
5515.0001.01
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 20°C
165 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
max. delivery
320 l/min
max. delivery pressure
4 bar
Delivery at 0,5 bar
305 l/min
Delivery at 1,0 bar
285 l/min
Delivery at 1,5 bar
260 l/min
Delivery at 2,0 bar
240 l/min
Delivery at 2,5 bar
215 l/min
Delivery at 3,0 bar
185 l/min
Delivery at 3,5 bar
150 l/min
Delivery at 4,0 bar
110 l/min
Delivery at 4,5 bar
50 l/min
Pump connection
G1 1/4 male
Cooling water connection
G1 1/4 male
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
min. filling capacity
17,5 l
Volume of expansion
50 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply (3 Phase)
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
** Overall dimensions WxDxH
Engineering Facts
13 facts · every claim linked to a page
Installation
The chiller requires cooling water with a differential pressure of at least 1 bar and a maximum pressure of 6 bar, so the site water supply must be verified before installation.
Insufficient differential pressure will prevent proper cooling and may cause the unit to trip on high temperature.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit is water-cooled and must be connected to a cooling water circuit with G1 1/4 male connections, so piping adapters must be planned.
Ensures correct fittings are available and avoids delays during commissioning.
Source
“Cooling water connection G1 1/4 male”
Operation
The cooling water inlet temperature must be between 5°C and 20°C; if it falls below the condensation point, the cooling water pipes inside the unit must be insulated.
Operating outside this range risks condensation, corrosion, or reduced cooling performance.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase, so the water supply must be sized for worst-case conditions.
Prevents undersizing the cooling water supply and ensures stable process temperature control.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water (e.g., low chloride, non-corrosive) should be used.
Incompatible water chemistry can cause corrosion, fouling, or leaks in the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance
The unit is classified as Class A, Group 1 for electromagnetic disturbance to EN55011, which may require additional filtering or separation from sensitive equipment.
Class A equipment is not intended for residential environments and may cause interference; plan EMC measures accordingly.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety
Leakage current exceeds 3.5 mA, so a reliable protective earth connection is mandatory and RCD selection must account for this.
Ensures electrical safety and correct earth leakage protection design.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug, so a suitable plug and connection must be provided on site.
Avoids delays and ensures the electrical installation is completed correctly.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.
Prevents operation outside safe limits that could damage the compressor or electronics.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The unit has an IP20 degree of protection, so it must be installed indoors and protected from water ingress and dust.
IP20 is not suitable for wet or dusty environments; installation location must be chosen accordingly.
Source
“Degree of Protection IP20”
Selection
The chiller uses R-744 (CO2) refrigerant with GWP 1 and is classified A1, H280, which affects refrigerant handling and safety requirements.
CO2 refrigerant operates at high pressure and requires specific safety measures and trained personnel.
Source
“R-744 (A1, H280)”
Installation
The overall dimensions are 918x963x1771 mm, and space requirements must be respected, so the installation site must accommodate this footprint and clearance.
Ensures the unit fits in the available space and allows for maintenance access.
Source
“Overall dimensions WxDxH ** 918x963x1771 mm”
Operation
The minimum filling capacity is 17.5 l and the expansion volume is 50 l, so the external circuit volume must be considered when selecting heat transfer fluid quantity.
Prevents underfilling or overfilling the system, which can affect temperature stability and pump performance.