The unit is rated for an operating temperature range of -20 to 40 °C, so it cannot be used outside this span.
Defines the process temperature window the chiller can cover.
Source
“Operating temperature range -20...40 °C”
| Parameter | Value |
|---|---|
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/20 |
| Parameter | Value |
|---|---|
| Order-No. | 3050.0024.01 |
| Operating temperature range | -20...40 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,5 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | I / NFL |
| Cooling power at ambient temperature +20°C | |
| at 15°C | 1 kW |
| at 0°C | 0,8 kW |
| at -10°C | 0,5 kW |
| at -20°C | 0,15 kW |
| Refrigeration machine | air-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump: | B |
| max. delivery | 25 l/min |
| max. delivery pressure | 2,5 bar |
| Delivery at 0,5 bar | 21 l/min |
| Delivery at 1,0 bar | 17 l/min |
| Delivery at 1,5 bar | 11 l/min |
| Delivery at 2,0 bar | 6 l/min |
| Pump connection | G3/4 male |
| min. filling capacity | 3,8 l |
| Volume of expansion | 1,7 l |
| Overall dimensions WxDxH ** | 350x496x622 mm |
| Net weight | 56 kg |
| sound pressure level +/- 4 dB(A) | 57 dB(A) |
| Power supply requirement | 208V 2~ 60Hz |
| max. current | 6,5 A |
| Fuse | 10 A |
** Overall dimensions WxDxH
The unit is rated for an operating temperature range of -20 to 40 °C, so it cannot be used outside this span.
Defines the process temperature window the chiller can cover.
“Operating temperature range -20...40 °C”
Cooling capacity drops sharply at low temperatures, from 1 kW at +15 °C to only 0.15 kW at -20 °C, so the load must be sized against the actual set point.
Prevents undersizing the chiller for low-temperature duty.
“at 15°C 1 kW at 0°C 0,8 kW at -10°C 0,5 kW at -20°C 0,15 kW”
The unit requires a 208 V two-phase 60 Hz supply with a 10 A fuse, so the site power must match this configuration.
Determines electrical supply and protection needed at the installation site.
“Power supply requirement 208V 2~ 60Hz max. current 6,5 A Fuse 10 A”
The pump connection is G3/4 male, so mating hoses and couplings must be G3/4 female.
Ensures correct plumbing connections are ordered.
“Pump connection G3/4 male”
The pump delivers 25 l/min max and 2.5 bar max, with flow falling to 6 l/min at 2.0 bar, so high-pressure-drop loops must be checked against the pump curve.
Allows verification that the pump can overcome the external circuit pressure drop.
“max. delivery 25 l/min max. delivery pressure 2,5 bar Delivery at 2,0 bar 6 l/min”
The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation precautions apply.
Informs safety assessment and refrigerant handling requirements.
“R-449A (A1, H280)”
The refrigerant has a GWP of 1397, which matters for F-gas reporting and environmental compliance.
Needed for refrigerant charge reporting and environmental permitting.
“Global Warming Potential (GWP) 1397”
The unit is IP20 and must be installed where ambient temperature stays between 5 and 40 °C.
Constrains the installation location and room conditions.
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Cooling capacity data are valid at 20 °C room temperature and may drop if ambient rises, so derating is needed in warm rooms.
Prevents overestimating capacity in non-20 °C environments.
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant pump specified.
Prevents chemical attack and pump failure from incompatible heat transfer fluids.
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Guides correct heat transfer fluid preparation for sub-zero operation.
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Three-phase devices below 63 A are supplied with cable but without plug, so a plug must be provided on site.
Avoids installation delays from missing mains plug.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Voltage and frequency tolerances are ±5% and ±2% respectively, but combined worst-case deviations in the same direction are not allowed.
Defines acceptable supply quality for reliable operation.
“-5% voltage and +2% frequency -> not allowed!”
The equipment is EMC Class A Group 1, which may require additional measures in residential or sensitive environments.
Informs EMC planning and site suitability.
“Classification (disturbance) to EN55011: Class A, Group 1”