Unichiller P025w-H Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller P025w-H chiller unit
  2. Spec pp. 1-2
    Performance, temperature, and dimensional data per DIN 12876
  3. p. 2 table, 16 rows
  4. p. 1 table, 31 rows

Technical data according to DIN 12876

ParameterValue
Consumption at water 15°C, flow -10°C72 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity3,8 l
Volume of expansion1,7 l
Overall dimensions WxDxH **420x487x579 mm
Net weight66 kg
sound pressure level +/- 4 dB(A)60 dB(A)
Power supply requirement220-240V 1~ 50Hz
max. current15 A
Fuse16 A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S606084

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller P025w-H — Technical data according to DIN 12876

ParameterValue
Order-No.3052.0048.01
Operating temperature range-10...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power at 240V2,1 kW
Heating power at 230V2 kW
Heating power at 220V1,8 kW
Cooling power at ambient temperature +20°C at 15°C2,5 kW
Cooling power at ambient temperature +20°C at 0°C2 kW
Cooling power at ambient temperature +20°C at -10°C1,2 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-290 (A3, H220)
Global Warming Potential (GWP)0,02
Refrigerant quantity0,18 kg
CO2 equivalent0,0 t
UN-numberUN 3358
Circulation pumpB
max. delivery25 l/min
max. delivery pressure2,5 bar
Delivery at 0,5 bar21 l/min
Delivery at 1,0 bar17 l/min
Delivery at 1,5 bar11 l/min
Delivery at 2,0 bar6 l/min
Pump connectionG3/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C84 l/h
Consumption at water 15°C, flow 0°C84 l/h

Cooling power values are given at ambient temperature +20°C for the respective coolant temperatures 15°C, 0°C and -10°C.

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller requires cooling water inlet temperature between 5°C and 20°C, so the facility water supply must be sized and controlled within this window.

Cooling water outside this range will reduce cooling capacity or cause condensation, affecting installation design and utility requirements.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

Cooling water differential pressure must be at least 1 bar and must not exceed 6 bar, so the supply/return piping and pressure regulation must be designed accordingly.

Insufficient differential pressure starves the water-cooled condenser; excessive pressure can damage the cooling circuit.

Source
“min. cooling water differential pressure 1 bar”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Incompatible water chemistry can corrode or foul these materials, so water quality must be checked before commissioning.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

If cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated.

Condensation on cold internal piping can cause water ingress and corrosion, so insulation is a mandatory installation measure in cold-water applications.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Safety

The unit uses refrigerant R-290 (A3, H220), a flammable natural refrigerant, which drives ATEX/ignition-source and ventilation considerations.

Flammable refrigerant classification affects room ventilation, ignition source control and service procedures during selection and installation.

Source
“R-290 (A3, H220)”
Safety

The plastic circulation pump is not resistant to acetone or polyglycols, so these fluids must not be used as heat transfer media.

Using an incompatible fluid will damage the pump, so fluid selection must avoid acetone and polyglycol-based media.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

This defines the recommended heat transfer fluid preparation for sub-zero operation, preventing freezing and damage.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Operation

The unit is rated for ambient temperatures from 5°C to 40°C, so the installation room must stay within this range.

Ambient temperature outside the range degrades cooling performance and may trip safety limits during operation.

Source
“max. ambient temperature 40 °C”
Performance

Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase, so utility capacity must account for worst-case water temperature.

Sizing the facility water supply only for 15°C inlet will under-deliver cooling at higher water temperatures.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Compliance

Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.

This constrains the acceptable power supply quality at the installation site and must be verified before connection.

Source
“-5% voltage and +2% frequency -> not allowed!”
Compliance

The unit is classified as EN55011 Class A, Group 1 for electromagnetic disturbance, which has implications for the electromagnetic environment of the installation.

Class A equipment is intended for industrial environments, so EMC compatibility with nearby sensitive equipment must be assessed.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit requires a 16 A fuse and draws a maximum current of 15 A on a 220-240V 1~ 50Hz supply.

This determines the electrical supply circuit, breaker rating and cabling required at the installation site.

Source
“max. current 15 A”
Installation

The unit has IP20 degree of protection, so it must be installed in a dry indoor location protected from water ingress.

IP20 limits installation to dry, protected environments and rules out washdown or outdoor locations.

Source
“Degree of Protection IP20”
Maintenance

The unit has a minimum filling capacity of 3.8 l and an expansion volume of 1.7 l, which sets the heat transfer fluid charge and expansion vessel sizing.

Knowing the minimum fill and expansion volume is needed to prepare the correct fluid charge and avoid overflow or cavitation.

Source
“min. filling capacity 3,8 l”