The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines whether the unit can cover the required process temperatures at all.
Source
“Operating temperature range -20...40 °C”
| Parameter | Value |
|---|---|
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/20 |
| Parameter | Value |
|---|---|
| Order-No. | 3059.0007.01 |
| Operating temperature range | -20...40 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,5 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | I / NFL |
| Cooling power at ambient temperature +20°C | |
| at 20°C | 10 kW |
| at 0°C | 8,7 kW |
| at -10°C | 5,8 kW |
| at -20°C | 4 kW |
| Refrigeration machine | air-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump: | E2 |
| max. delivery | 140 l/min |
| max. delivery pressure | 5,3 bar |
| Delivery at 2,8 bar | 126 l/min |
| Delivery at 3,0 bar | 124 l/min |
| Delivery at 3,5 bar | 115 l/min |
| Delivery at 4,0 bar | 103 l/min |
| Delivery at 4,5 bar | 83 l/min |
| Delivery at 5,0 bar | 43 l/min |
| Pump connection | G1 1/4 male |
| min. filling capacity | 18 l |
| Volume of expansion | 48 l |
| Overall dimensions WxDxH ** | 740x1160x1165 mm |
| Power supply (3 Phase) | 460V 3~ 60Hz |
| Pressure equipment category | Art. 4.3 PED |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
** Overall dimensions WxDxH
The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines whether the unit can cover the required process temperatures at all.
“Operating temperature range -20...40 °C”
Cooling capacity drops with falling temperature (10 kW at +20 °C down to 4 kW at -20 °C), so size the unit for the coldest operating point.
Prevents undersizing when the process runs at low temperatures.
“at 20°C 10 kW at 0°C 8,7 kW at -10°C 5,8 kW at -20°C 4 kW”
Cooling capacity is specified at 20 °C room temperature and may fall if ambient rises, so account for the actual installation room.
Ambient conditions in the plant room directly affect achievable cooling.
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
The unit is air-cooled, so the installation site must supply adequate air flow and respect the stated space requirements.
Air-cooled chillers need clearance and ventilation to reject heat.
“** Please respect space requirements. See operating conditions at www.huber-online.com”
The pump connection is G1 1/4 male, so hoses and fittings must match this thread.
Determines the connection hardware needed for the external circuit.
“Pump connection G1 1/4 male”
The unit requires a 460 V three-phase 60 Hz supply, so the site power must match this configuration.
Wrong supply voltage or phase count makes the unit unusable.
“Power supply (3 Phase) 460V 3~ 60Hz”
Voltage and frequency tolerances are ±5 % and ±2 % but must not be combined in the unfavorable direction, so verify supply quality.
Out-of-tolerance supply can trip or damage the compressor and pump.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
External branch circuit protection per UL 489 is required, so the electrical installation must include it.
Mandatory for a compliant and safe electrical installation.
“External branch circuit protection according to UL 489 required.”
Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be provided on site.
Affects the electrical hook-up scope and materials.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation rules apply.
Relevant for safety assessment and room ventilation requirements.
“R-449A (A1, H280)”
The refrigerant has a GWP of 1397, which matters for F-gas reporting and environmental compliance.
High-GWP refrigerant affects legal obligations and leak monitoring.
“Global Warming Potential (GWP) 1397”
The unit is IP20, so it must be installed in a dry, protected location away from water and dust ingress.
IP20 limits where the chiller can safely be placed.
“Degree of Protection IP20”
The minimum ambient temperature is 5 °C, so the installation room must not fall below this.
Cold rooms can prevent proper operation and starting.
“min. ambient temperature 5 °C”
The expansion tank is atmospheric open and has a cover, so it must be checked and kept covered during operation.
Open expansion tanks need periodic level checks and protection from contamination.
“cover expansion tank”