The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Determines electrical infrastructure and whether a transformer or different model is needed.
Source
“Power supply (3 Phase) 460V 3~ 60Hz”
| Parameter | Value |
|---|---|
| Consumption at water 15°C, flow -20°C | 324 l/h |
| min. cooling water differential pressure | 1 bar |
| max. cooling water pressure | 6 bar |
| min. filling capacity | 18 l |
| Volume of expansion | 48 l |
| Overall dimensions WxDxH ** | 940x1290x1130 mm |
| Power supply (3 Phase) | 460V 3~ 60Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/21 |
** Please respect space requirements. See operating conditions at www.huber-online.com
| Parameter | Value |
|---|---|
| Order-No. | 3039.0040.01 |
| Operating temperature range | -20...100 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,2 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | III / FL |
| Heating power | 2 kW |
| Cooling power at ambient temperature +20°C at 100°C | 23 kW |
| Cooling power at ambient temperature +20°C at 20°C | 23 kW |
| Cooling power at ambient temperature +20°C at 0°C | 13,5 kW |
| Cooling power at ambient temperature +20°C at -10°C | 9 kW |
| Cooling power at ambient temperature +20°C at -20°C | 5,5 kW |
| Refrigeration machine | water-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump | E2 |
| max. delivery | 140 l/min |
| max. delivery pressure | 5,3 bar |
| Delivery at 2,8 bar | 126 l/min |
| Delivery at 3,0 bar | 124 l/min |
| Delivery at 3,5 bar | 115 l/min |
| Delivery at 4,0 bar | 103 l/min |
| Delivery at 4,5 bar | 83 l/min |
| Delivery at 5,0 bar | 43 l/min |
| Pump connection | G1 1/4 male |
| Cooling water connection | G3/4 male |
| Consumption at water 15°C, flow 20°C | 744 l/h |
| Consumption at water 15°C, flow 0°C | 540 l/h |
| Consumption at water 15°C, flow -10°C | 414 l/h |
The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Determines electrical infrastructure and whether a transformer or different model is needed.
“Power supply (3 Phase) 460V 3~ 60Hz”
External branch circuit protection according to UL 489 is required, so a suitable breaker must be installed in the supply circuit.
Necessary for code-compliant and safe electrical installation.
“External branch circuit protection according to UL 489 required.”
Three-phase devices drawing less than 63 A are supplied with cable but without a plug, so the installer must provide a suitable plug or hard-wired connection.
Affects electrical termination planning and bill of materials.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
The unit is designed for cooling water intake between 5 °C and 20 °C, so the facility water supply must stay within this range.
Out-of-range cooling water can reduce cooling capacity or cause condensation issues.
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion damage inside the unit.
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the water quality must be compatible with these materials.
Guides selection of water treatment and avoids corrosion or fouling.
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
The cooling water differential pressure must be at least 1 bar and must not exceed 6 bar.
Ensures adequate flow for heat rejection without overpressurizing the circuit.
“min. cooling water differential pressure 1 bar”
The maximum cooling water pressure is 6 bar, so the supply must be regulated or limited accordingly.
Protects the cooling water circuit from overpressure damage.
“max. cooling water pressure 6 bar”
The unit requires a minimum filling capacity of 18 l and has an expansion volume of 48 l.
Determines heat transfer fluid volume needed and expansion tank sizing.
“min. filling capacity 18 l”
The overall dimensions are 940x1290x1130 mm, so the installation space must accommodate this footprint and height.
Needed for floor space planning and access clearance.
“Overall dimensions WxDxH ** 940x1290x1130 mm”
The ambient temperature must remain between 5 °C and 40 °C for proper operation.
Operating outside this range may affect performance and reliability.
“min. ambient temperature 5 °C”
The maximum ambient temperature is 40 °C, so the room must not exceed this limit.
High ambient temperature reduces cooling capacity and can trip the unit.
“max. ambient temperature 40 °C”
Cooling power drops as temperature decreases, from 23 kW at 20 °C to 5.5 kW at -20 °C, so capacity must be checked at the actual operating temperature.
Prevents undersizing when selecting the chiller for low-temperature duty.
“at -20°C 5,5 kW”
The circulation pump delivers a maximum of 140 l/min at up to 5.3 bar, so system pressure drop must be checked against the pump curve.
Ensures adequate flow through the external circuit at its pressure drop.
“max. delivery 140 l/min”