Product introduction and general description of the Unimotive GL 20w unit
Specpp. 1-2
Technical data, performance figures and operating parameters per DIN 12876
p. 2table, 26 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
2100 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Net weight
612 kg
Power supply requirement
400V 3~ 50Hz
max. current
55,7 A
Fuse
3x63A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S583202
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
28 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
25 kW
at -20°C
18,6 kW
at -30°C
11 kW
at -40°C
6,8 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Refrigerant quantity
3,5 kg
CO2 equivalent
0,0 t
UN-number
UN 2857
Circulation pump:
MK pump
max. delivery
201 l/min
Engineering Facts
13 facts · every claim linked to a page
Selection
The unit is intended for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.
Determines whether the unit suits the intended automotive test fluid and low-temperature duty.
Source
“constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C”
Installation
The cooling water supply must be kept between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Cooling water conditions directly affect achievable cooling capacity and condensation risk.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
The cooling water circuit requires a differential pressure between 1 and 4 bar and must not exceed 6 bar.
Plant cooling water supply must be verified before installation to avoid insufficient flow or overpressure.
Source
“min. cooling water differential pressure 1 bar”
Installation
Three-phase devices below 63 A are supplied with cable but without a plug, so site wiring must be planned.
Affects electrical installation scope and whether a plug must be procured separately.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Site power quality must be checked to avoid invalid supply combinations and equipment damage.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
Leakage current exceeds 3.5 mA, which matters for protective earthing and RCD selection.
Electrical protection design must account for high leakage current per applicable standards.
Source
“Attention: leakage current > 3,5mA”
Installation
The unit requires 400 V 3~ 50 Hz supply with maximum current 55.7 A and 3x63 A fusing.
Determines feeder sizing, breaker rating and electrical room requirements.
Source
“max. current 55,7 A”
Installation
Pump connections are M38x1.5 male and mating pipework must use ball socket per DIN 3863 and sleeve nut per DIN 3870.
Ensures correct hose/pipe fittings are ordered and leak-free connections are made.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation
Cooling capacity drops as cooling water temperature rises, and cooling water flow rate may need to increase.
Performance planning must account for actual site cooling water temperature and available flow.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Selection
The unit uses R-744 (CO2) refrigerant with GWP 1 and 3.5 kg charge, relevant for refrigerant regulations.
Refrigerant type and charge affect compliance, safety classification and service requirements.
Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Installation
Ambient temperature must stay between 5°C and 40°C, and IP20 protection limits installation environment.
Room conditions and ingress protection must match the installation location.
Source
“max. ambient temperature 40 °C”
Operation
Minimum filling capacity is 8.9 l and expansion tank capacity is 19.9 l, defining the required fluid volume.
Needed to prepare the correct heat transfer fluid quantity and expansion volume.
Source
“min. filling capacity 8,9 l”
Maintenance
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable water quality is required.
Water quality and treatment must be compatible to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”