Unimotive GL 30w

Contents

  1. Overview p. 1
    Product introduction and general description of the unit
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 25 rows
  4. p. 1 table, 27 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C3100 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Net weight820 kg
Power supply requirement460V 3~ 60Hz
max. current57 A
Fuse3x63A
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S589778

** Please respect space requirements. See operating conditions at www.huber-online.com

Unimotive GL 30w — Technical data according to DIN 12876

ParameterValue
Order-No.5009.0003.01
Operating temperature range-45...95 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C35 kW
at -20°C22 kW
at -30°C14 kW
at -40°C8,5 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Refrigerant quantity8,7 kg
CO2 equivalent0,0 t
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than plain-water loops.

Confirms the intended heat transfer fluid and application envelope before specifying the unit.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

The cooling water supply must be kept between 5°C and 20°C, and pipes must be insulated if the water can drop below the condensation point.

Defines the facility cooling water requirement and condensation/insulation precaution at the installation site.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

Cooling water differential pressure must stay between 1 bar and 4 bar, with a maximum cooling water pressure of 6 bar.

Sets the allowable cooling water circuit pressure window for correct flow and safe operation.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit requires a 460 V 3-phase 60 Hz supply with 57 A max current and 3x63 A fusing, and three-phase devices below 63 A are delivered with cable but without plug.

Drives electrical supply sizing, branch protection and the need to procure a plug/connection on site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

Leakage current exceeds 3.5 mA and an external branch circuit protection per UL 489 is required.

Mandates proper external branch protection and grounding design for the electrical installation.

Source
“Attention: leakage current > 3,5mA”
Compliance

Voltage and frequency tolerances are ±5% and ±2% respectively, but they may not be combined in the unfavorable direction.

Prevents specifying the unit on a supply where combined voltage/frequency deviation exceeds EN60034-1 limits.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

Pump connections are M38x1.5 male with bore shape Y (60°) per DIN 3863, requiring matching ball socket and sleeve nut per DIN 3870.

Ensures correct mating fittings and hoses are ordered for the process circuit.

Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.

Limits fluid selection at low temperatures where viscosity rises and pump performance degrades.

Source
“max. permissible kin. viscosity 200 mm²/s”
Installation

The unit needs at least 8.9 l filling capacity and has a 19.9 l expansion tank, with a maximum system pressure of 6 bar.

Sizes the fluid charge and expansion volume for the external loop.

Source
“min. filling capacity 8,9 l”
Installation

Ambient temperature must be kept between 5°C and 40°C, and the unit is IP20 rated.

Defines room conditions and ingress protection limits for siting the equipment.

Source
“max. ambient temperature 40 °C”
Performance

Cooling power falls from 35 kW at 0°C to 8.5 kW at -40°C, so low-temperature duty must be checked against the load curve.

Prevents oversizing assumptions at deep negative temperatures during selection.

Source
“at -40°C 8,5 kW”
Operation

Cooling water consumption is 3100 l/h at 15°C water and 0°C flow, and cooling power drops as cooling water temperature rises.

Sizes the facility cooling water supply and anticipates derating with warmer water.

Source
“Consumption at water 15°C, flow 0°C 3100 l/h”
Safety

The refrigerant is R-744 (A1, H280) with GWP 1 and 8.7 kg charge, and the unit is safety class III / FL.

Informs refrigerant handling, room ventilation and safety classification requirements.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Maintenance

The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility to avoid corrosion and fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”