Introduces the Unistat GL 570w unit and its main features
Specpp. 1-2
Performance, temperature range, and dimensional specifications per DIN 12876
Specp. 2
Detailed technical parameters according to DIN 12876 standard
p. 2table, 16 rows
p. 1table, 32 rows
Technical data according to DIN 12876
Parameter
Value
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Unistat GL 570w — Technical data according to DIN 12876
Parameter
Value
Order-No.
5041.0001.01
Operating temperature range
-50...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
48 kW
Cooling power with Thermooil at 200°C
57 kW
Cooling power with Thermooil at 100°C
57 kW
Cooling power with Thermooil at 20°C
57 kW
Cooling power with Ethanol at 0°C
50 kW
Cooling power with Ethanol at -20°C
35 kW
Cooling power with Ethanol at -40°C
19 kW
Cooling power with Ethanol at -50°C
12 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
Circulation pump: MK pump
max. delivery
196 l/min
max. delivery pressure
2,5 bar
Delivery at 0,5 bar
175 l/min
Delivery at 1,0 bar
152 l/min
Delivery at 1,5 bar
123 l/min
Delivery at 2,0 bar
86 l/min
Значения приведены дословно по тексту страницы; строки «Cooling power with Thermooil» и «Cooling power with Ethanol» объединяют соответствующие температурные подпункты.
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase supply, so the site must provide a 3~ 50 Hz feed sized for the 48 kW heater.
Determines electrical infrastructure, cable sizing and whether the facility can support the unit at all.
Source
“Power supply requirement
400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so the installer must provide a suitable plug or hard-wired connection.
Affects electrical installation scope and procurement of the mating connector.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Cooling water must be supplied at 1–4 bar differential and no more than 6 bar, with 5–20 °C intake, so the site cooling loop must be checked before commissioning.
Insufficient or excessive cooling water pressure will prevent rated cooling performance or damage the water circuit.
Source
“min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar”
Installation
If cooling water is colder than the condensation point, the cooling water pipes inside the unit must be insulated.
Prevents condensation and corrosion/electrical risk when using cold site water.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Rated cooling capacities are valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential, and will drop at higher cooling water temperatures.
Prevents overestimating available cooling power when site conditions differ from the rating basis.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and treatment to avoid corrosion or fouling of the heat exchanger.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Operation
Voltage and frequency tolerances are ±5 % and ±2 % but must not combine in the same direction, so supply quality must be verified.
Out-of-tolerance supply can trip the unit or reduce lifetime; the example clarifies the allowed combinations.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Compliance
The unit is EMC Class A Group 1, so it is intended for industrial environments and may cause interference in residential areas.
Affects installation location and EMC planning in mixed-use or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety
The unit is safety class III / FL per DIN 12876 and has adjustable overtemperature protection, which must be set for the application.
Overtemperature protection setting is a key safety measure for the thermal fluid and connected load.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection
The pump delivers 196 l/min max at 2.5 bar, dropping to 86 l/min at 2.0 bar, so system pressure drop must be matched to the pump curve.
Ensures the external circuit can achieve the required flow at its actual pressure loss.
Pump connections are M38x1.5 male and cooling water connections are G3/4 male, so mating hoses and adapters must be ordered accordingly.
Prevents delays and leaks from mismatched connections during installation.
Source
“Pump connection
M38x1,5 male”
Operation
Ambient temperature must stay between 5 °C and 40 °C, and the unit is IP20, so it must be installed in a dry, protected location.
Defines the allowable plant room conditions and protection against water/dust ingress.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Maintenance
The refrigerant is R-744 (A1, H280) with GWP 1 and UN 2857, so service and transport must follow the corresponding safety data.
Affects refrigerant handling, labeling and emergency procedures during service.
Source
“Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)”
Selection
Minimum filling capacity is 8.9 l and the expansion tank holds 19.9 l, so the external loop volume plus unit volume must be considered when selecting fluid quantity.
Ensures sufficient thermal fluid is ordered and the expansion volume is adequate for the application.
Source
“min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l”