Product introduction and general description of the Unistat GL P570w unit
Specpp. 1-2
Technical data, performance figures and operating parameters per DIN 12876
p. 2table, 19 rows
p. 1table, 28 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unistat GL P570w (Order-No.: 5041.0002.01)
Characteristic
Value
Operating temperature range
-50...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
48 kW
Cooling power with Thermooil at 200°C
57 kW
Cooling power with Thermooil at 100°C
57 kW
Cooling power with Thermooil at 20°C
57 kW
Cooling power with Ethanol at 0°C
50 kW
Cooling power with Ethanol at -20°C
35 kW
Cooling power with Ethanol at -40°C
19 kW
Cooling power with Ethanol at -50°C
12 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
Circulation pump: MK pump max. delivery
201 l/min
Circulation pump: MK pump max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Таблица приведена в исходном виде (характеристика — значение); данные дословно по тексту страницы.
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase 50 Hz supply, so the site must provide a suitable three-phase power connection.
Determines electrical infrastructure and whether the installation site can support the unit.
Source
“Power supply requirement
400V 3~ 50Hz”
Installation
The cooling water connection is G3/4 male and requires a differential pressure between 1 and 4 bar, with maximum cooling water pressure 6 bar.
Needed to design the cooling water supply and ensure adequate flow and pressure without overpressurizing the unit.
Source
“Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar”
Installation
The unit is water-cooled and must be supplied with cooling water between 5 °C and 20 °C; below the condensation point the cooling water pipes must be insulated.
Cooling water temperature affects cooling capacity and requires insulation to prevent condensation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling capacity drops as cooling water temperature rises, and the required cooling water flow rate may increase.
The published cooling capacities are valid only at 15 °C cooling water inlet and 1 bar differential pressure, so system design must account for actual site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The pump connection is M38x1,5 male and pipework or flexible hoses must use ball socket according to DIN 3863 and sleeve nut according to DIN 3870.
Ensures correct mating of external circuit piping and hoses to the circulation pump.
Source
“Pump connection
M38x1,5 male”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.
Limits the choice of heat transfer fluid and ensures pump performance and safe operation.
Source
“max. permissible kin. viscosity
100 mm²/s”
Safety
The maximum system pressure is 6 bar, so the external circuit and connected components must be rated accordingly.
Prevents overpressure of the unit and connected external circuit.
Source
“max. System pressure
6 bar”
Installation
The unit has protection degree IP20 and must be operated in ambient temperatures between 5 °C and 40 °C.
Defines environmental limits and protection against ingress, affecting installation location.
Source
“Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Installation
The unit requires minimum filling capacity of 8.9 l and has an expansion tank filling capacity of 19.9 l.
Needed to size the external circuit volume and ensure sufficient heat transfer fluid.
Source
“min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l”
Compliance
Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.
Ensures the electrical supply stays within safe operating limits and avoids invalid tolerance combinations.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices with current consumption less than 63 A are supplied with cable but without plug.
The installer must provide a suitable plug or direct connection for the three-phase supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The refrigerant is R-744 (A1, H280) with GWP 1 and UN number UN 2857, so refrigerant safety and transport classifications apply.
Affects safety measures, labeling, and handling of the refrigerant during installation and service.
Source
“Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857”
Operation
The circulation pump delivers 201 l/min maximum and 5.3 bar maximum delivery pressure, with reduced flow at higher pressure.
Used to verify that the external circuit pressure drop and required flow are within pump capability.