Product introduction and general description of CS 50 unit
Specp. 2
Technical data per DIN 12876, performance and dimensions
p. 1table, 31 rows
CS 50 by Van der Heijden — Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-20...15 °C
temperature set point / display
colour LED Touchscreen
Internal temperature sensor
Pt100
Temperature stability at -10°C
0,5 K
Safety classification
I / NFL
Cooling power at ambient temperature 20°C
at 15°C
8 kW
at 10°C
5 kW
at 0°C
4,2 kW
at -10°C
3,5 kW
at -20°C
2 kW
Refrigeration machine
air-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Refrigerant quantity
4 kg
CO2 equivalent
5,59 t
Circulation pump:
max. delivery
70 l/min
max. delivery pressure
3,7 bar
Pump connection
G3/4 male
min. filling capacity
100 l
max. filling capacity
110 l
Overall dimensions WxDxH **
680x730x1520 mm
Net weight
199 kg
sound pressure level +/- 4 dB(A)
63 dB(A)
Power supply (3 Phase)
400V 3~ 50Hz
max. current (3 Phase)
9 A
Fuse (3 phase)
3x16A
Degree of Protection
IP52
min. ambient temperature
5 °C
max. ambient temperature
32 °C
from Serial-No.:
1.0/24
** Technical details and dimensions are subject to change. No liability is accepted for errors or omissions. Illustrations can deviate from the original.
Engineering Facts
12 facts · every claim linked to a page
Selection
The chiller's cooling capacity is rated at 20°C ambient and will drop if ambient temperature rises, so size the unit with margin for the actual room temperature.
Prevents undersizing when the installation room runs warmer than 20°C.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
Three-phase devices drawing less than 63 A are supplied with cable but no plug, so the installer must provide a suitable plug and connection.
Affects electrical installation planning and bill of materials.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be respected simultaneously; a -5% voltage combined with +2% frequency is not allowed.
Ensures the supply quality at the site is compatible before commissioning.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit requires a 3x16 A fuse on a 400 V three-phase supply, which must be provided at the installation site.
Defines the electrical protection and supply capacity needed for installation.
Source
“Fuse (3 phase)
3x16A”
Installation
The chiller must be installed where ambient temperature stays between 5°C and 32°C.
Site conditions outside this range can impair operation and cooling performance.
Source
“min. ambient temperature
5 °C
max. ambient temperature
32 °C”
Operation
The flow rate can be adjusted using the manual bypass valve on the back of the chiller, allowing matching to the application.
Important for setting correct circulation during commissioning.
Source
“The flow rate can be adjusted via the manual bypass valve on the backside of the chiller.”
Operation
The recommended heat transfer fluid is a 50:50 water–monoethylene glycol mixture.
Using the correct fluid protects the pump and ensures performance within the -20…15°C range.
Source
“Recommended thermofluid: Water - Monoethylene Glycol 50:50”
Safety
The refrigerant R-449A is classified A1 but carries hazard statement H280, so refrigerant handling and ventilation precautions apply.
Relevant for safety assessment and service planning of the refrigeration circuit.
Source
“R-449A (A1, H280)”
Cumplimiento
The equipment is EMC-classified as Class A, Group 1, which has implications for use in residential environments.
Class A equipment may cause interference in domestic settings; important for site selection.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Cumplimiento
The unit is certified for industrial process refrigeration under US-SNAP, confirming its intended end-use.
Confirms regulatory suitability for industrial process cooling applications.
Source
“The US-SNAP end-use for this equipment is the industrial process refrigeration.”
Installation
Space requirements around the unit must be respected, with details available in the operating conditions online.
Air-cooled condensers need adequate clearance for airflow and service access.
Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Selection
The unit has a minimum filling capacity of 100 l and maximum of 110 l, constraining the external loop volume.
Ensures the application loop volume fits within the chiller's tank and circuit limits.
Source
“min. filling capacity
100 l
max. filling capacity
110 l”