The unit is rated for an operating temperature range of -30 to 50 °C, so it must be selected only for applications within these limits.
Defines the process temperature window the cooler can support.
Source
“Operating temperature range -30...50 °C”
| Parameter | Value |
|---|---|
| Operating temperature range | -30...50 °C |
| Safety classification | I / NFL |
| Cooling power at 15°C | 0,6 kW |
| Cooling power at 0°C | 0,47 kW |
| Cooling power at -20°C | 0,12 kW |
| Refrigeration machine | air-cooled, natural |
| refrigerant | |
| Refrigerant (ASHRAE, GHS) | R-290 (A3, H220) |
| Global Warming Potential (GWP) | 0,02 |
| Refrigerant quantity | 0,08 kg |
| fluid connection | M16x1 male |
| Overall dimensions WxDxH ** | 280x340x465 mm |
| Net weight | 30 kg |
| Power supply requirement | 220-240V 1~/2~ 50/60Hz |
| max. current | 3 A |
| min. Fuse | 10A |
| max. Fuse | 16A |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No. | 460283 |
** Please respect space requirements. See operating conditions at www.huber-online.com
The unit is rated for an operating temperature range of -30 to 50 °C, so it must be selected only for applications within these limits.
Defines the process temperature window the cooler can support.
“Operating temperature range -30...50 °C”
Cooling capacity drops significantly at lower temperatures, from 0.6 kW at 15 °C to 0.12 kW at -20 °C, so sizing must use the capacity at the actual operating point.
Prevents undersizing when the application runs at low temperatures.
“Cooling power at 15°C 0,6 kW at 0°C 0,47 kW at -20°C 0,12 kW”
The refrigerant is R-290 (A3, H220), a flammable natural refrigerant, which requires appropriate safety measures and awareness during installation and service.
Flammable refrigerant classification affects site safety and service procedures.
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
The fluid connection is M16x1 male, so mating hoses and fittings must match this thread.
Ensures correct hydraulic connection hardware is ordered.
“fluid connection M16x1 male”
The power supply requirement is 220-240 V 1~/2~ 50/60 Hz with max current 3 A, so the electrical supply and protection must be sized accordingly.
Needed to plan the electrical connection and breaker rating.
“Power supply requirement 220-240V 1~/2~ 50/60Hz max. current 3 A”
The minimum fuse is 10 A and maximum fuse is 16 A, so the upstream protection must fall within this range.
Avoids nuisance tripping or inadequate protection.
“min. Fuse 10A max. Fuse 16A”
The degree of protection is IP20, so the unit must be installed in a dry indoor environment protected from water and dust ingress.
Restricts installation location and environmental exposure.
“Degree of Protection IP20”
The ambient temperature must be between 5 °C and 40 °C, so the installation room must be kept within this range.
Ambient limits affect reliable operation and cooling performance.
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Output data are valid for a room temperature of 20 °C, and higher ambient temperature may reduce cooling capacity, so capacity margins should account for actual room conditions.
Prevents overestimating capacity in warm installation rooms.
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed, so supply quality must be verified.
Ensures the electrical supply stays within the allowed envelope.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
The equipment is classified as EN55011 Class A, Group 1 for disturbance, so it is intended for industrial electromagnetic environments rather than residential ones.
Affects EMC compatibility and suitability for the installation site.
“Classification (disturbance) to EN55011: Class A, Group 1”
Single/two-phase devices are delivered with a power cable and country-specific plug that must be specified at ordering, so the correct plug variant must be requested.
Prevents delivery with the wrong plug for the site.
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Space requirements must be respected as stated in the operating conditions, so clearance around the unit must be planned before installation.
Insufficient clearance can impair air-cooled operation and access.
“Please respect space requirements. See operating conditions at www.huber-online.com”