Introduces the CS 550-H OD unit and its main features
Specpp. 1-2
Lists performance, temperature, and dimensional data per DIN 12876
p. 2table, 15 rows
p. 1table, 40 rows
Technical data according to DIN 12876
Parameter
Value
max. delivery
125 l/min
max. delivery pressure
4,7 bar
Pump connection
G1 male
min. filling capacity
160 l
Bath volume advance warning
175 l
max. filling capacity
195 l
Overall dimensions WxDxH **
1400x1000x1800 mm
Net weight
715 kg
sound pressure level +/- 4 dB(A)
79 dB(A)
Power supply (3 Phase)
460V 3~ 60Hz
max. current (3 Phase)
73 A
Fuse (3 phase)
3x90A
min. ambient temperature
-20 °C
max. ambient temperature
50 °C
from Serial-No.:
236124
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-20...85 °C
temperature set point / display
colour LED Touchscreen
Internal temperature sensor
Pt100
Temperature stability at -10°C
2 K
Interface digital
RS232
Safety classification
I / NFL
Heating power
17 kW
Kälteleistung bei Umgebungstemperatur 5°C
at 15°C
61 kW
at 10°C
54 kW
at 0°C
29 kW
at -10°C
15 kW
at -20°C
9 kW
Cooling power at ambient temperature 20°C
at 15°C
70 kW
at 10°C
60 kW
at 0°C
33 kW
at -10°C
20 kW
at -20°C
12 kW
Kälteleistung bei Umgebungstemperatur 35°C
at 15°C
63 kW
at 10°C
55 kW
at 0°C
29 kW
at -10°C
16 kW
at -20°C
9 kW
Kälteleistung bei Umgebungstemperatur 40°C
at 15°C
55 kW
at 10°C
49 kW
at 0°C
25 kW
at -10°C
13 kW
at -20°C
7 kW
Kälteleistung bei Umgebungstemperatur 50°C
at 15°C
44 kW
at 10°C
41 kW
at 0°C
19 kW
at -10°C
9 kW
Refrigeration machine
air-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Refrigerant quantity
23 kg
CO2 equivalent
32,13 t
Engineering Facts
14 facts · every claim linked to a page
Selection
The chiller's cooling capacity is strongly ambient-dependent, so it must be sized against the actual site ambient temperature rather than a single nominal figure.
Prevents undersizing when the unit is installed in a warm room or outdoors.
Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation
The unit is rated for outdoor mounting down to -20 °C ambient, which affects enclosure, frost protection and siting decisions.
Allows outdoor installation but requires planning for low ambient conditions.
Source
“Suitable for outside mounting (min. environmental temperature -20°C)”
Installation
Above +35 °C ambient the cooling power is reduced, so the installation location must be checked against the 50 °C maximum.
Defines the ambient threshold above which performance derating begins.
Source
“Reduction of cooling power above +35°C environmental temperature”
Installation
The electrical components are IP54, which sets the minimum protection level expected at the installation site.
Confirms suitability for dusty or splash-exposed outdoor locations.
Source
“Protection classification of the electrical components IP54”
Installation
Three-phase units above 63 A are delivered without cable and without plug, so the customer must provide the full power connection.
Affects electrical installation scope and cost before delivery.
Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Installation
Voltage and frequency tolerances are coupled, so a -5 % voltage combined with +2 % frequency is not acceptable.
Prevents connecting the chiller to a supply outside the permitted combined tolerance.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The remote control panel is connected via a 20 m cable, which constrains where the operating panel can be located.
Determines cable routing and panel placement during site planning.
Source
“Delivered with remote control: operating panel connected via 20m cable”
Operation
The flow rate is set by a manual bypass valve on the rear of the chiller, so access to the back is needed for adjustment.
Requires rear clearance for commissioning and flow balancing.
Source
“The flow rate can be adjusted via the manual bypass valve on the backside of the chiller.”
Operation
The recommended heat transfer fluid is a 50:50 water-monoethylene glycol mix, which must be used to match the -20 °C range.
Ensures freeze protection and correct viscosity over the operating range.
Source
“Recommended thermofluid: Water - Monoethylene Glycol 50:50”
Operation
The bath has a minimum filling of 160 l and a maximum of 195 l, with a warning at 175 l, defining the usable fluid inventory.
Sets the fluid volume to procure and the level limits for safe operation.
Source
“min. filling capacity”
Safety
The refrigerant is R-449A classified A1 with GHS hazard H280, so leak and pressure safety measures apply.
Informs refrigerant handling, labeling and ventilation requirements.
Source
“R-449A (A1, H280)”
Safety
The unit carries 23 kg of R-449A equal to 32.13 t CO2 equivalent, which triggers refrigerant reporting obligations.
Needed for F-gas/CO2-equivalent registration and leak-check scheduling.
Source
“CO2 equivalent”
Cumplimiento
The equipment is EMC Class A Group 1, so it is intended for industrial environments and may disturb residential areas.
Restricts installation to industrial EMC environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Performance
The pump delivers up to 125 l/min at 4.7 bar through a G1 male connection, which sizes the external circuit.
Defines the hydraulic capability and connection size for the process loop.