Installation
The chiller requires cooling water with a differential pressure between 3 and 6 bar, so the site water supply must be verified before installation.
Insufficient or excessive cooling water pressure will prevent proper operation or damage the unit.
Source
“min. cooling water differential pressure
3 bar
max. cooling water pressure
6 bar”
Installation
Cooling water inlet temperature must be kept between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Out-of-range cooling water temperature reduces cooling capacity and can cause condensation and corrosion.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Selection
The unit uses flammable R-290 refrigerant (A3, H220), which affects safety classification and site requirements.
Flammable refrigerant requires appropriate safety measures and may restrict installation location.
Source
“Refrigerant (ASHRAE, GHS)
R-290 (A3, H220)”
Selection
The plastic pump is not resistant to acetone or polyglycols, so these media must be avoided or a more resistant pump specified.
Using incompatible media will damage the pump and void reliable operation.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
The permissible return line temperature is 80°C, which defines the upper limit for the application.
Exceeding this temperature can damage the unit and must be considered when selecting the process.
Source
“Permissible temperature in return line 80 °C”
Installation
The electrical supply must be 208-240V single or two-phase at 50/60Hz with a fuse between 10A and 16A.
Correct supply and fuse rating are essential for safe and reliable electrical installation.
Source
“Power supply requirement
208-240V 1~/2~ 50/60Hz
max. current
4 A
min. Fuse
10A
max. Fuse
16A”
Installation
Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage and +2% frequency is not allowed.
Non-compliant supply conditions can cause malfunction or damage and must be checked at the site.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The whisper mode reduces sound pressure to 51 dB(A) but also reduces pump delivery to 14 l/min and 0.2 bar.
If low noise is required, the reduced pump performance must be acceptable for the process.
Source
“Pump data for whisper mode:
Delivery rate:
14 l/min
Delivery pressure:
0.2 bar”
Installation
The unit has IP20 protection, so it must be installed in a dry environment protected from water ingress.
IP20 is not water-resistant and limits installation to indoor dry locations.
Source
“Degree of Protection
IP20”
Operation
Ambient temperature must be between 5°C and 40°C for proper operation.
Operating outside this range can affect cooling performance and reliability.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.
Incompatible water quality can cause corrosion or fouling, affecting maintenance and lifetime.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection
Cooling power drops from 0.8 kW at 15°C to 0.3 kW at -20°C, which must be considered for low-temperature applications.
Available cooling capacity decreases significantly at lower temperatures, affecting process design.
Source
“Cooling power
at 15°C
0,8 kW
at 0°C
0,6 kW
at -10°C
0,45 kW
at -20°C
0,3 kW”