Unichiller 017Tw-H Technical Datasheet

Contenido

  1. Overview p. 1
    Product introduction and general description of the chiller unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating parameters per DIN 12876
  3. p. 2 table, 8 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Overall dimensions WxDxH **400x440x1230 mm
sound pressure level +/- 4 dB(A)64 dB(A)
Power supply requirement208V 2~ 60Hz
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/21

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 017Tw-H (Order-No.: 3013.0070.01)

ParameterValue
Operating temperature range-10...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power1,6 kW
Cooling power at 15°C1,7 kW
Cooling power at 0°C0,9 kW
Cooling power at -10°C0,4 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Circulation pumpB
max. delivery30 l/min
max. delivery pressure3,8 bar
Delivery at 0,12 bar29 l/min
Delivery at 0,5 bar25 l/min
Delivery at 1,0 bar21 l/min
Delivery at 1,5 bar17 l/min
Delivery at 2,0 bar13,5 l/min
Delivery at 2,5 bar10 l/min
Delivery at 3,0 bar6,5 l/min
Pump connectionG3/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C53 l/h
Consumption at water 15°C, flow 0°C40 l/h
Consumption at water 15°C, flow -10°C25 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity2,5 l
Volume of expansion4 l

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.

Determines whether the site's cooling water loop can supply adequate pressure and whether a booster pump or pressure reducer is needed.

Source
“min. cooling water differential pressure 1 bar”
Installation

Cooling water inlet temperature must be between 5 °C and 20 °C, and pipes must be insulated if the water temperature can fall below the dew point.

Defines the acceptable cooling water supply conditions and the need for pipe insulation to prevent condensation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling capacity drops as cooling water temperature rises, and the required cooling water flow rate may increase.

Affects sizing of the cooling water supply and expected performance at the actual site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility checks to avoid corrosion or damage to the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento

Voltage tolerance is ±5% only when frequency tolerance is simultaneously ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.

Ensures the electrical supply at the installation site stays within the permitted voltage and frequency window.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices drawing less than 63 A are supplied with a cable but without a plug, so a suitable plug must be provided on site.

Affects electrical installation planning and the need to procure and fit a plug.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The unit is rated for ambient temperatures from 5 °C to 40 °C.

Defines the allowable room temperature range where the chiller can be installed and operated.

Source
“min. ambient temperature 5 °C”
Safety

The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation precautions apply.

Informs safety measures for refrigerant handling and room ventilation during installation and service.

Source
“R-449A (A1, H280)”
Selection

The unit has a global warming potential of 1397, which matters for refrigerant regulations and environmental reporting.

Relevant for compliance with refrigerant regulations and for environmental impact assessment during selection.

Source
“Global Warming Potential (GWP) 1397”
Installation

The pump connection is G3/4 male and the cooling water connection is G1/2 male, so matching hose couplings are required.

Determines the fittings and hoses needed for process and cooling water connections.

Source
“Pump connection G3/4 male”
Operation

The minimum filling capacity is 2.5 l and the expansion volume is 4 l, which sets the minimum heat transfer fluid charge.

Needed to plan the heat transfer fluid volume and expansion tank capacity for the application.

Source
“min. filling capacity 2,5 l”
Installation

The unit has degree of protection IP20, so it must be protected from water and dust ingress.

Restricts installation location to dry, protected areas and affects enclosure or room requirements.

Source
“Degree of Protection IP20”