Unichiller 055T Technical Datasheet

Contenido

  1. Overview p. 1
    Introduces the Unichiller 055T chiller and its main features
  2. Spec pp. 1-2
    Performance, temperature, cooling capacity and connection data per DIN 12876
  3. p. 2 table, 10 rows
  4. p. 1 table, 35 rows

Technical data according to DIN 12876

ParameterValue
Overall dimensions WxDxH **640x825x1606 mm
Net weight281 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current7 A
Fuse16 A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.1/26

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller 055T — Technical data according to DIN 12876

ParameterValue
Order-No.3015.0093.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
Temperature stability at -10°C0,5 K
Safety classificationI / NFL
Cooling power at 15°C5,5 kW
Cooling power at 0°C2,3 kW
Cooling power at -10°C0,8 kW
Cooling power at -20°C0,2 kW
Refrigeration machineair-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-290 (A3, H220)
Global Warming Potential (GWP)0,02
Refrigerant quantity0,95 kg
CO2 equivalent0,0 t
UN-numberUN 3358
Circulation pump:C3
max. delivery100 l/min
max. delivery pressure5,6 bar
Delivery at 0,3 bar97 l/min
Delivery at 1,0 bar90 l/min
Delivery at 1,5 bar84 l/min
Delivery at 2,0 bar77 l/min
Delivery at 2,5 bar71 l/min
Delivery at 3,0 bar64 l/min
Delivery at 3,5 bar57 l/min
Delivery at 4,0 bar48 l/min
Delivery at 4,5 bar39 l/min
Delivery at 5,0 bar27 l/min
Delivery at 5,5 bar8 l/min
Pump connectionG1 1/4 male
min. filling capacity5 l
Volume of expansion7,5 l

Engineering Facts

13 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.

Defines the application window and excludes processes requiring lower or higher temperatures.

Source
“Operating temperature range -20...40 °C”
Selection

Cooling capacity drops sharply at low temperatures, from 5.5 kW at 15 °C to only 0.2 kW at -20 °C.

Sizing must be based on the actual operating temperature, not the nominal maximum.

Source
“at 15°C 5,5 kW at 0°C 2,3 kW at -10°C 0,8 kW at -20°C 0,2 kW”
Safety

The refrigerant is R-290 (propane, A3, H220), a flammable natural refrigerant, which affects installation and safety planning.

Flammable refrigerant requires attention to ventilation, ignition sources and local regulations.

Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
Installation

The unit requires a 400 V three-phase supply with a 16 A fuse and draws up to 7 A.

Determines the electrical supply, cabling and protection needed at the installation site.

Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current 7 A Fuse 16 A”
Installation

Three-phase devices below 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.

Prevents delays at commissioning because the customer must supply and fit the plug.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit is IP20 and must be installed in an environment between 5 °C and 40 °C ambient temperature.

IP20 offers no water protection and the ambient limits constrain the installation location.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Performance

Cooling capacity is specified at 20 °C room temperature and may drop if the ambient temperature rises.

Sizing must account for the real ambient conditions at the installation site.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but not simultaneously in opposite directions.

Defines the acceptable power quality and the limits for generator or weak-grid operation.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Cumplimiento

The equipment is EMC class A, group 1, which is intended for industrial environments.

Class A equipment may cause interference in residential areas and is intended for industrial use.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The pump connection is G1 1/4 male, and a matching hose coupling is included.

Determines the hose or piping adapters needed for the external circuit.

Source
“Pump connection G1 1/4 male”
Operation

The minimum filling capacity is 5 l and the expansion volume is 7.5 l, which sets the heat transfer fluid charge.

Ensures the external loop is filled correctly and the expansion tank can absorb volume changes.

Source
“min. filling capacity 5 l Volume of expansion 7,5 l”
Selection

The unit is intended for externally closed applications, which constrains the hydraulic circuit design.

Prevents use in open or pressure-less circuits that the design does not support.

Source
“For externally closed applications.”
Maintenance

The warranty is 4 years but requires registration.

Registration must be completed to secure the extended warranty coverage.

Source
“4-year warranty - registration required.”