Unichiller 055Tw Technical Datasheet

Contenido

  1. Overview p. 1
    Introduces the Unichiller 055Tw chiller and its main features
  2. Spec pp. 1-2
    Lists performance, temperature, and physical specifications per DIN 12876
  3. p. 2 table, 11 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Volume of expansion7,5 l
Overall dimensions WxDxH **640x660x1606 mm
Net weight250 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)7,5 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.1/26

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 15°C5,5 kW
Cooling power at 0°C3 kW
Cooling power at -10°C1,5 kW
Cooling power at -20°C0,4 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-290 (A3, H220)
Global Warming Potential (GWP)0,02
Refrigerant quantity0,6 kg
CO2 equivalent0,0 t
UN-numberUN 3358
Circulation pumpC3
max. delivery102 l/min
max. delivery pressure6 bar
Delivery at 1,0 bar93 l/min
Delivery at 2,0 bar83 l/min
Delivery at 3,0 bar72 l/min
Delivery at 4,0 bar58 l/min
Delivery at 5,0 bar40 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C330 l/h
Consumption at water 15°C, flow 0°C260 l/h
Consumption at water 15°C, flow -10°C180 l/h
min. cooling water differential pressure0,6 bar
max. cooling water pressure6 bar
min. filling capacity5,9 l

Engineering Facts

12 facts · every claim linked to a page
Selection

The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 0.6 bar and a maximum pressure of 6 bar.

Ensures the site's cooling water system can meet the required pressure range for proper operation.

Source
“min. cooling water differential pressure 0,6 bar max. cooling water pressure 6 bar”
Installation

The unit must be connected to a three-phase 400 V 50 Hz supply with a 3x16 A fuse and a maximum current of 7.5 A.

Electrical supply and protection must be sized accordingly before installation.

Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current (3 Phase) 7,5 A Fuse (3 phase) 3x16A”
Installation

Three-phase devices with current consumption less than 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.

Avoids delays and ensures the correct power connection is available at commissioning.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The cooling water inlet temperature must be between 5 °C and 20 °C; if it falls below the condensation point, the cooling water pipes inside the unit must be insulated.

Prevents condensation and corrosion damage; defines the acceptable cooling water temperature window.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

The stated cooling power is valid only at a room temperature of 20 °C, cooling water inlet of 15 °C, and 0.6 bar differential pressure; higher cooling water temperatures reduce cooling power and may increase flow rate.

Allows correct interpretation of the cooling capacity data and avoids oversizing or undersizing.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 0,6 bar differential pressure between cooling water inlet and -outlet.”
Safety

The refrigerant is R-290 (propane), classified A3 with GHS H220 (extremely flammable), so appropriate safety measures for flammable refrigerants are required.

Affects site safety classification, ventilation, and handling procedures during installation and maintenance.

Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
Cumplimiento

The equipment is classified as Class A, Group 1 for electromagnetic disturbance according to EN55011, which may require specific EMC measures in sensitive environments.

Informs EMC planning and potential restrictions when installing near sensitive equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit has a protection degree of IP20 and must be operated within an ambient temperature range of 5 °C to 40 °C.

Defines environmental limits and ingress protection for the installation location.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The overall dimensions are 640 x 660 x 1606 mm and the net weight is 250 kg, requiring adequate floor space and structural support.

Needed for site planning, access routes, and floor loading considerations.

Source
“Overall dimensions WxDxH ** 640x660x1606 mm Net weight 250 kg”
Operation

Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage with +2% frequency are not allowed.

Ensures the power supply quality is within acceptable limits to avoid malfunction or damage.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible cooling water may be used.

Prevents corrosion and fouling by selecting appropriate water quality and treatment.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Selection

The minimum filling capacity is 5.9 l and the expansion volume is 7.5 l, which must be considered when preparing the heat transfer circuit.

Ensures enough heat transfer fluid is available and the expansion tank is adequately sized.

Source
“min. filling capacity 5,9 l”