The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Electrical supply must match before ordering and installation.
Source
“Power supply (3 Phase) 460V 3~ 60Hz”
| Parameter | Value |
|---|---|
| Cooling water connection | G3/4 male |
| Consumption at water 15°C, flow 15°C | 400 l/h |
| Consumption at water 15°C, flow 0°C | 191 l/h |
| Consumption at water 15°C, flow -10°C | 89 l/h |
| min. cooling water differential pressure | 1 bar |
| max. cooling water pressure | 6 bar |
| min. filling capacity | 6,5 l |
| Volume of expansion | 5,5 l |
| Overall dimensions WxDxH ** | 600x600x1450 mm |
| Net weight | 372 kg |
| sound pressure level +/- 4 dB(A) | 65 dB(A) |
| Power supply (3 Phase) | 460V 3~ 60Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/21 |
** Please respect space requirements. See operating conditions at www.huber-online.com
| Characteristic | Unichiller 110Tw-H |
|---|---|
| Order-No. | 3027.0069.01 |
| Operating temperature range | -20...100 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,2 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | III / FL |
| Heating power | 2 kW |
| Cooling power at 15°C | 11 kW |
| Cooling power at 0°C | 6 kW |
| Cooling power at -10°C | 2,7 kW |
| Cooling power at -20°C | 2 kW |
| Refrigeration machine | water-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| UN-number | UN 2857 |
| Circulation pump | C3 |
| max. delivery | 97 l/min |
| max. delivery pressure | 6,5 bar |
| Delivery at 0,35 bar | 108 l/min |
| Delivery at 0,5 bar | 106 l/min |
| Delivery at 1,0 bar | 101 l/min |
| Delivery at 1,5 bar | 96 l/min |
| Delivery at 2,0 bar | 90 l/min |
| Delivery at 2,5 bar | 84 l/min |
| Delivery at 3,0 bar | 78 l/min |
| Delivery at 3,5 bar | 71 l/min |
| Delivery at 4,0 bar | 64 l/min |
| Delivery at 4,5 bar | 56 l/min |
| Delivery at 5,0 bar | 48 l/min |
| Delivery at 5,5 bar | 38 l/min |
| Delivery at 6,0 bar | 24 l/min |
| Pump connection | G1 1/4 male |
The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Electrical supply must match before ordering and installation.
“Power supply (3 Phase) 460V 3~ 60Hz”
The unit is water-cooled and needs cooling water connections of G3/4 male with a minimum differential pressure of 1 bar.
Cooling water piping and pressure must be planned for installation.
“Cooling water connection G3/4 male”
Cooling water pressure must not exceed 6 bar, so a pressure reducer may be required.
Prevents overpressure damage to the cooling water circuit.
“max. cooling water pressure 6 bar”
The unit is designed for cooling water intake between 5°C and 20°C, and lower temperatures require insulating the cooling water pipes.
Operating outside this range or without insulation can cause condensation issues.
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.
Performance must be derated if site cooling water is warmer than 15°C.
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water should be used.
Water quality must be compatible to avoid corrosion or damage.
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed.
Site power quality must be checked against these limits.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
External branch circuit protection according to UL 489 is required.
Electrical installation must include UL 489 branch protection.
“External branch circuit protection according to UL 489 required.”
Three-phase devices with current consumption less than 63A are supplied with cable but without plug.
The installer must provide a suitable plug or hardwiring.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
The unit must be operated within an ambient temperature range of 5°C to 40°C.
Ambient conditions affect reliable operation and must be verified.
“min. ambient temperature 5 °C”
The refrigerant is R-449A with GHS classification A1, H280, and UN number UN 2857.
Refrigerant safety data must be known for handling and emergency planning.
“R-449A (A1, H280)”
The unit has a minimum filling capacity of 6.5 l and expansion volume of 5.5 l.
Heat transfer fluid volume must be planned for commissioning and maintenance.
“min. filling capacity 6,5 l”
The unit weighs 372 kg net, so floor loading and lifting equipment must be considered.
Installation site must support the weight and allow safe handling.
“Net weight 372 kg”
The circulation pump delivers up to 97 l/min and 6.5 bar, with flow decreasing at higher pressure.
External circuit pressure drop must be matched to the pump curve.
“max. delivery 97 l/min”