The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this exact power configuration.
Determines electrical infrastructure and whether a transformer or different model is needed.
Source
“Power supply (3 Phase) 460V 3~ 60Hz”
| Parameter | Value |
|---|---|
| max. cooling water pressure | 6 bar |
| min. filling capacity | 18 l |
| Volume of expansion | 48 l |
| Overall dimensions WxDxH ** | 940x1290x1130 mm |
| Power supply (3 Phase) | 460V 3~ 60Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/21 |
** Please respect space requirements. See operating conditions at www.huber-online.com
| Parameter | Value |
|---|---|
| Order-No. | 3039.0038.01 |
| Operating temperature range | -20...100 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,2 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | III / FL |
| Heating power | 2 kW |
| Cooling power at ambient temperature +20°C at 100°C | 23 kW |
| Cooling power at ambient temperature +20°C at 20°C | 23 kW |
| Cooling power at ambient temperature +20°C at 0°C | 13,5 kW |
| Cooling power at ambient temperature +20°C at -10°C | 9 kW |
| Cooling power at ambient temperature +20°C at -20°C | 5,5 kW |
| Refrigeration machine | water-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump | E1 |
| max. delivery | 56 l/min |
| max. delivery pressure | 3,8 bar |
| Förderleistung bei 0,17 bar | 53 l/min |
| Delivery at 0,5 bar | 51 l/min |
| Delivery at 1,0 bar | 46 l/min |
| Delivery at 1,5 bar | 40 l/min |
| Delivery at 2,0 bar | 34 l/min |
| Delivery at 2,5 bar | 27 l/min |
| Delivery at 3,0 bar | 18 l/min |
| Pump connection | G1 1/4 male |
| Cooling water connection | G3/4 male |
| Consumption at water 15°C, flow 20°C | 744 l/h |
| Consumption at water 15°C, flow 0°C | 540 l/h |
| Consumption at water 15°C, flow -10°C | 414 l/h |
| Consumption at water 15°C, flow -20°C | 324 l/h |
| min. cooling water differential pressure | 1 bar |
The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this exact power configuration.
Determines electrical infrastructure and whether a transformer or different model is needed.
“Power supply (3 Phase) 460V 3~ 60Hz”
External branch circuit protection per UL 489 must be provided by the installer.
Affects panel design and compliance with local electrical codes.
“External branch circuit protection according to UL 489 required.”
Three-phase devices drawing less than 63 A are supplied with cable but no plug, so a suitable plug must be sourced separately.
Prevents delays at commissioning due to missing plug and clarifies scope of delivery.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Cooling water inlet temperature must be between 5 °C and 20 °C, and pipes must be insulated if below the condensation point.
Defines cooling water supply requirements and condensation risk mitigation.
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
A minimum cooling water differential pressure of 1 bar is required for proper operation.
Ensures adequate flow through the water-cooled refrigeration circuit.
“min. cooling water differential pressure 1 bar”
Cooling water pressure must not exceed 6 bar.
Protects the cooling water circuit from overpressure damage.
“max. cooling water pressure 6 bar”
The unit requires a minimum filling capacity of 18 l and has an expansion volume of 48 l.
Determines heat transfer fluid volume needed and expansion tank sizing.
“min. filling capacity 18 l”
The unit must be installed in an environment between 5 °C and 40 °C ambient temperature.
Affects room selection and ventilation/cooling requirements.
“min. ambient temperature 5 °C”
The unit has IP20 protection, so it must be kept in a dry, indoor location free from water ingress.
Restricts installation to protected indoor environments.
“Degree of Protection IP20”
Cooling capacity drops as cooling water temperature rises, and flow rate may need to increase.
Affects performance expectations and cooling water system sizing.
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality should be used.
Guides selection of cooling water treatment to avoid corrosion and fouling.
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Ensures the site power quality is within acceptable limits for warranty and safe operation.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
The equipment is classified as Class A, Group 1 for electromagnetic disturbance per EN55011.
Informs EMC planning and potential interference with sensitive equipment nearby.
“Classification (disturbance) to EN55011: Class A, Group 1”
The refrigerant R-449A has a GHS hazard H280 (pressurized gas) and a GWP of 1397.
Requires awareness of pressurized refrigerant hazards and environmental impact for selection and service.
“R-449A (A1, H280)”