Unichiller 250Tw Technical Datasheet

Contenido

  1. Overview p. 1
    Introduces the Unichiller 250Tw chiller unit
  2. Spec pp. 1-2
    Performance, temperature, and dimensional data per DIN 12876
  3. p. 2 table, 13 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
max. cooling water pressure6 bar
min. filling capacity15 l
Volume of expansion22 l
Overall dimensions WxDxH **760x800x1615 mm
Net weight378 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)22 A
Fuse (3 phase)3x25A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S562954

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 250Tw (Order-No. 3057.0005.01)

ParameterValue
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 15°C25 kW
Cooling power at 0°C18 kW
Cooling power at -10°C11 kW
Cooling power at -20°C6 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity2,6 kg
CO2 equivalent3,6 t
Circulation pumpD3
max. delivery210 l/min
max. delivery pressure4,7 bar
Delivery at 1,1 bar202 l/min
Delivery at 1,5 bar193 l/min
Delivery at 2,0 bar179 l/min
Delivery at 2,5 bar159 l/min
Delivery at 3,0 bar140 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar77 l/min
Delivery at 4,5 bar31 l/min
Pump connectionG1 1/4 male
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 15°C852 l/h
Consumption at water 15°C, flow 0°C786 l/h
Consumption at water 15°C, flow -10°C594 l/h
Consumption at water 15°C, flow -20°C438 l/h
min. cooling water differential pressure1 bar

Order-No.: 3057.0005.01

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a minimum cooling water differential pressure of 1 bar between inlet and outlet.

Ensures the cooling water supply can provide adequate flow through the condenser.

Source
“min. cooling water differential pressure 1 bar”
Installation

Cooling water intake temperature must be between 5°C and 20°C; below the condensation point the cooling water pipes in the unit must be insulated.

Defines the permissible cooling water supply conditions and insulation requirement to prevent condensation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

The maximum cooling water pressure is 6 bar.

Prevents overpressure damage to the cooling water circuit.

Source
“max. cooling water pressure 6 bar”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without plug.

The installer must provide a suitable plug and connection for the 22 A three-phase supply.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination of -5% voltage with +2% frequency is not allowed.

Defines acceptable supply quality for reliable operation of the 400V 3~ 50Hz unit.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Selection

Cooling power depends on flow temperature: 25 kW at 15°C, 18 kW at 0°C, 11 kW at -10°C and 6 kW at -20°C.

Allows sizing the chiller for the required heat load at the actual process temperature.

Source
“at 15°C 25 kW at 0°C 18 kW at -10°C 11 kW at -20°C 6 kW”
Selection

The circulation pump delivers 210 l/min maximum and 202 l/min at 1.1 bar, dropping to 31 l/min at 4.5 bar.

Needed to match pump flow and pressure to the external circuit resistance.

Source
“max. delivery 210 l/min”
Selection

The refrigerant is R-449A with GWP 1397 and a charge of 2.6 kg, corresponding to 3.6 t CO2 equivalent.

Relevant for refrigerant regulations, leak detection and environmental compliance.

Source
“R-449A (A1, H280)”
Operation

The unit is intended for externally closed applications.

The external circuit must be closed; open-loop applications are not supported.

Source
“For externally closed applications.”
Operation

The minimum filling capacity is 15 l and the expansion volume is 22 l.

Determines the minimum heat transfer fluid volume required for safe operation.

Source
“min. filling capacity 15 l”
Operation

Ambient temperature must be between 5°C and 40°C.

Defines the allowable installation room temperature range.

Source
“min. ambient temperature 5 °C”
Safety

The unit has safety classification I / NFL according to DIN 12876.

Indicates the safety category relevant for use with flammable or non-flammable fluids.

Source
“Safety classification I / NFL”
Cumplimiento

The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011.

Class A equipment may require EMC precautions in residential or light-industrial environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Maintenance

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used.

Guides water quality selection to avoid corrosion and fouling of the mixed-material cooling circuit.

Source
“Please use suitable cooling water.”