Unichiller 600Tw — Technical data according to DIN 12876
Parameter
Value
Order-No.
3031.0003.01
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,5 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 15°C
60 kW
Cooling power at 0°C
45 kW
Cooling power at -10°C
30 kW
Cooling power at -20°C
20 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
6 kg
CO2 equivalent
8,4 t
Circulation pump
D3
max. delivery
234 l/min
max. delivery pressure
4,9 bar
Delivery at 1,3 bar
197 l/min
Delivery at 1,5 bar
192 l/min
Delivery at 2,0 bar
178 l/min
Delivery at 2,5 bar
158 l/min
Delivery at 3,0 bar
137 l/min
Delivery at 3,5 bar
115 l/min
Delivery at 4,0 bar
86 l/min
Delivery at 4,5 bar
40 l/min
Pump connection
G1 1/4 male
Cooling water connection
G1 1/4 male
min. cooling water differential pressure
1,5 bar
max. cooling water pressure
6 bar
min. filling capacity
12,7 l
Volume of expansion
7 l
Overall dimensions WxDxH **
1000x1100x1635 mm
** см. сноску в оригинале (в тексте страницы пояснение отсутствует)
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller requires cooling water with a differential pressure of at least 1.5 bar and a maximum supply pressure of 6 bar.
Ensures the water-cooled condenser receives adequate flow and the facility's water supply does not exceed the unit's pressure rating.
Source
“min. cooling water differential pressure 1,5 bar”
Installation
The unit is designed for cooling water intake temperatures between 5°C and 20°C, and pipes must be insulated if water temperature can fall below the condensation point.
Defines the permissible cooling water supply temperature window and a condensation-prevention requirement for the installation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling capacity is rated at 60 kW at 15°C and drops as cooling water temperature rises, so the actual capacity depends on site water conditions.
Prevents overestimating available cooling capacity when the facility's cooling water is warmer than the rating conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The three-phase unit draws up to 45 A and requires a 3x50 A fuse, supplied with cable but without a plug.
Informs the electrical installer that a suitable plug and 50 A protection must be provided on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Cumplimiento
Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.
Guides verification of the site power quality before commissioning to avoid invalid supply combinations.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
The refrigerant is R-449A (A1, H280) with a GWP of 1397 and a CO2 equivalent of 8.4 t, which matters for leak detection and environmental reporting.
Identifies the refrigerant safety group and greenhouse impact for handling, leak checks and F-gas obligations.
Source
“R-449A (A1, H280)”
Operation
The unit is rated IP20 and must be operated in ambient temperatures from 5°C to 40°C.
Sets the allowable room conditions and ingress protection level for siting the chiller.
Source
“min. ambient temperature 5 °C”
Installation
The chiller is water-cooled and CFC/HCFC-free, so it needs a cooling water circuit rather than air cooling.
Confirms the need for a cooling water supply and return connection at the installation site.
Source
“water-cooled, CFC- and HCFC-free”
Installation
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water should be used.
Warns that water quality must be compatible with the listed wetted materials to avoid corrosion or fouling.
Source
“Please use suitable cooling water.”
Selection
The pump delivers 234 l/min maximum and 197 l/min at 1.3 bar, with pressure-dependent flow data provided for system sizing.
Allows matching the circulation pump curve to the external circuit's pressure drop and required flow.
Source
“max. delivery 234 l/min”
Installation
The minimum filling capacity is 12.7 l and the expansion volume is 7 l, which must be considered when charging heat transfer fluid.
Determines the minimum fluid charge and expansion allowance for the external loop.
Source
“min. filling capacity 12,7 l”
Cumplimiento
The equipment is classified for electromagnetic disturbance as EN55011 Class A, Group 1.
Indicates EMC class for industrial environments and informs site EMC assessment.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”