Product name and general introduction to the chiller unit
Specp. 2
Technical data according to DIN 12876 standard
p. 1table, 27 rows
Unichiller GL 075w — Technical data according to DIN 12876
Parameter
Value
Order-No.
5506.0005.01
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 20°C
7,5 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
max. delivery
50 l/min
max. delivery pressure
3,5 bar
Pump connection
G1 1/4 male
Cooling water connection
G1/2 male
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
Volume of expansion
9,5 l
Overall dimensions WxDxH **
550x760x1455 mm
Power supply (3 Phase)
460V 3~ 60Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.
1.0/26
** Technical details and dimensions are subject to change. No liability is accepted for errors or omissions. Illustrations can deviate from the original.
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller requires cooling water with a differential pressure of at least 1 bar and a maximum supply pressure of 6 bar.
Ensures the cooling water circuit can provide adequate flow and pressure without exceeding component limits.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit is water-cooled and must be connected to a cooling water supply with G1/2 male connections.
Determines the piping and fittings needed for installation.
Source
“Cooling water connection G1/2 male”
Operation
Cooling water inlet temperature must be between 5°C and 20°C; below the condensation point, cooling water pipes inside the unit must be insulated.
Operating outside this range can cause condensation, reduced cooling capacity, or increased water flow requirements.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power is rated at 7.5 kW at 20°C, but higher cooling water temperatures reduce capacity and may require increased flow.
Affects sizing and expected performance under actual site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible cooling water should be used.
Prevents corrosion or damage from incompatible water chemistry.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento
Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations like -5% voltage and +2% frequency are not allowed.
Ensures the power supply stays within safe operating limits for the compressor and electronics.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
External branch circuit protection according to UL 489 is required.
Mandatory for electrical safety and code compliance in the installation.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices with current consumption less than 63A are supplied with cable but without a plug.
Installer must provide a suitable plug or hardwired connection.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The unit uses R-744 refrigerant, which is classified A1 but has a GHS hazard statement H280 (contains gas under pressure).
Requires awareness of pressure hazard and proper handling during service.
Source
“R-744 (A1, H280)”
Operation
The ambient temperature must be between 5°C and 40°C for proper operation.
Operating outside this range may affect performance or reliability.
Source
“min. ambient temperature 5 °C”
Selection
The chiller has a maximum delivery of 50 l/min and maximum delivery pressure of 3.5 bar.
Needed to match the external circuit's flow and pressure requirements.
Source
“max. delivery 50 l/min”
Installation
The pump connection is G1 1/4 male.
Determines the fittings required for the process loop.