Unichiller P015 OLÉ Technical Data

Contenido

  1. Overview p. 1
    Product name and cover page of the datasheet
  2. Spec p. 2
    Technical data according to DIN 12876

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -20 to 40 °C, so process requirements outside this window cannot be met.

Defines the application envelope and excludes processes needing lower or higher temperatures.

Source
“Operating temperature range -20...40 °C”
Performance

Cooling capacity drops from 1.5 kW at 15 °C to 0.3 kW at -20 °C, so the required heat load must be checked at the actual operating temperature.

Sizing on nominal capacity alone will undersize the unit at low temperatures.

Source
“at 15°C 1,5 kW at 0°C 1 kW at -10°C 0,7 kW at -20°C 0,3 kW”
Performance

Cooling capacity is valid at 20 °C room temperature and may drop as ambient temperature rises, so installation room conditions affect performance.

Ventilation and ambient conditions in the installation room must be planned for.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit requires a 220-240 V single-phase 50 Hz supply with 8.5 A max current and a 16 A fuse.

Determines electrical supply, cabling and protection device sizing at the installation site.

Source
“Power supply requirement 220-240V 1~ 50Hz max. current 8,5 A Fuse 16 A”
Installation

Voltage and frequency tolerances are ±5% and ±2% but must not be combined in the unfavorable direction, so supply quality must be verified.

Prevents installation on unstable or out-of-tolerance power networks.

Source
“-5% voltage and +2% frequency -> not allowed!”
Safety

The refrigerant is R-290 (A3, H220), a flammable natural refrigerant, so ignition sources and ventilation in the installation area must be considered.

Affects site safety assessment, ventilation and hazardous-area restrictions.

Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
Operation

The plastic pump is not resistant to acetone or polyglycols, so these media must not be used as heat transfer fluid.

Prevents chemical attack and premature pump failure when selecting the heat transfer fluid.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

Guides correct heat transfer fluid preparation for sub-zero operation.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation

The pump connection is G3/4 male, so mating hoses and fittings must match this thread.

Ensures correct hydraulic connection hardware is ordered and installed.

Source
“Pump connection G3/4 male”
Performance

Pump delivery falls from 21 l/min at 0.5 bar to 6 l/min at 2.0 bar, so system pressure drop directly limits available flow.

The external circuit pressure drop must be matched to the pump curve during selection.

Source
“at 0,5 bar 21 l/min at 1,0 bar 17 l/min at 1,5 bar 11 l/min at 2,0 bar 6 l/min”
Installation

The unit has IP20 protection, so it must be installed in a dry indoor location protected from water and dust ingress.

Restricts installation environment and enclosure requirements.

Source
“Degree of Protection IP20”
Installation

Ambient temperature at the installation site must stay between 5 °C and 40 °C.

Defines allowable room conditions and rules out outdoor or extreme environments.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Maintenance

Minimum filling capacity is 3.8 l and the expansion tank is 1.7 l, so the external loop volume and fluid charge must be planned accordingly.

Prevents underfilling and ensures expansion volume is adequate for the loop.

Source
“min. filling capacity 3,8 l expansion tank 1,7 l”
Cumplimiento

The equipment is classified Class A, Group 1 for electromagnetic disturbance, which has implications for the electromagnetic environment at the installation site.

Class A equipment may require EMC measures in residential or sensitive environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”