Unichiller P075-H Technical Datasheet

Contenido

  1. Overview p. 1
    Introduces the Unichiller P075-H chiller unit
  2. Spec p. 2
    Performance and technical data per DIN 12876
  3. p. 2 table, 13 rows
  4. p. 1 table, 32 rows

Technical data according to DIN 12876

ParameterValue
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **740x1160x1165 mm
Net weight311 kg
sound pressure level +/- 4 dB(A)61 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)13,5 A
Fuse (3 phase)3x16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S522520

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller P075-H — Technical data according to DIN 12876

ParameterValue
Order-No.3040.0034.01
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at ambient temperature +20°C
at 100°C7,5 kW
at 20°C7,5 kW
at 0°C5,3 kW
at -10°C3,3 kW
at -20°C1,8 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,03 kg
CO2 equivalent1,4 t
Circulation pump:E2
max. delivery130 l/min
max. delivery pressure5,7 bar
Delivery at 2,4 bar116 l/min
Delivery at 2,5 bar115 l/min
Delivery at 3,0 bar108 l/min
Delivery at 3,5 bar100 l/min
Delivery at 4,0 bar92 l/min
Delivery at 4,5 bar80 l/min
Delivery at 5,0 bar59 l/min
Delivery at 5,5 bar20 l/min
Pump connectionG1 1/4 male

Строка «Cooling power at ambient temperature +20°C» напечатана как заголовок группы; её значение пустое, далее идут подпункты по температурам.

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a three-phase 400 V supply with a 16 A fuse per phase, so the electrical installation must be sized accordingly.

Determines the site power distribution, cable sizing and breaker rating before installation.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so the customer must provide and fit the plug.

Affects procurement and electrical hook-up planning; a plug must be sourced separately.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit is rated IP20, so it must be installed in a dry indoor location protected from water and dust ingress.

Restricts installation environment and rules out washdown or outdoor siting.

Source
“Degree of Protection IP20”
Operation

Ambient temperature must stay between 5 °C and 40 °C, and cooling capacity may drop if ambient rises above 20 °C.

Room conditions directly affect achievable cooling performance and must be checked at the design stage.

Source
“If the ambient temperature rises, the cooling capacity may drop.”
Performance

Cooling capacity falls from 7.5 kW at 20 °C to 1.8 kW at -20 °C, so low-temperature duty needs a much larger unit margin.

Sizing at the coldest operating point prevents under-capacity at low temperatures.

Source
“at -20°C 1,8 kW”
Selection

The pump delivers only 20 l/min at 5.5 bar versus 130 l/min at free delivery, so high-pressure-drop loops need careful pump-curve checking.

Ensures the circulation pump can meet the flow demand of a high-impedance external circuit.

Source
“Delivery at 5,5 bar 20 l/min”
Installation

The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread size.

Determines the hose couplings and adapters needed for the external circuit.

Source
“Pump connection G1 1/4 male”
Safety

The unit uses refrigerant R-449A with GWP 1397 and a CO2 equivalent of 1.4 t, which matters for leak monitoring and F-gas obligations.

Triggers refrigerant-handling, leak-check and documentation requirements at the installation site.

Source
“CO2 equivalent 1,4 t”
Safety

The refrigerant is classified A1 with hazard statement H280, so it is non-flammable but stored under pressure.

Informs risk assessment and ventilation/pressure-safety measures for the refrigerant circuit.

Source
“R-449A (A1, H280)”
Operation

The unit is intended for externally closed applications, so an open external circuit is not permitted.

Prevents selecting the chiller for an open-loop process that would not suit its expansion tank design.

Source
“For externally closed applications.”
Maintenance

Minimum filling capacity is 18 l and expansion volume is 48 l, so the external loop volume must be checked against these limits.

Ensures the system has enough heat-transfer fluid and expansion room for safe operation.

Source
“min. filling capacity 18 l”
Cumplimiento

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are explicitly not allowed.

Guides power-quality assessment of the supply before commissioning the unit.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

The unit emits 61 dB(A) sound pressure, so acoustic planning and personnel exposure should be considered at the installation site.

Affects placement relative to work areas and any noise-control measures.

Source
“sound pressure level +/- 4 dB(A) 61 dB(A)”
Selection

The unit is classified as pressure equipment category Art. 4.3 PED, which defines its regulatory status for commissioning.

Determines which pressure-equipment compliance requirements apply at the site.

Source
“Pressure equipment category Art. 4.3 PED”