Unichiller P230w

Contenido

  1. Overview p. 1
    Introduces the Unichiller P230w chiller model and its intended use
  2. Spec pp. 1-2
    Performance, temperature, and dimensional data according to DIN 12876
  3. p. 2 table, 9 rows
  4. p. 1 table, 32 rows

Technical data according to DIN 12876

ParameterValue
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **940x1290x1130 mm
Power supply (3 Phase)460V 3~ 60Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/21

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller P230w — Technical data according to DIN 12876

ParameterValue
Order-No.3039.0039.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at ambient temperature +20°C at 20°C23 kW
Cooling power at ambient temperature +20°C at 0°C13,5 kW
Cooling power at ambient temperature +20°C at -10°C9 kW
Cooling power at ambient temperature +20°C at -20°C5,5 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Circulation pumpE2
max. delivery140 l/min
max. delivery pressure5,3 bar
Delivery at 2,8 bar126 l/min
Delivery at 3,0 bar124 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar103 l/min
Delivery at 4,5 bar83 l/min
Delivery at 5,0 bar43 l/min
Pump connectionG1 1/4 male
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 20°C744 l/h
Consumption at water 15°C, flow 0°C540 l/h
Consumption at water 15°C, flow -10°C414 l/h
Consumption at water 15°C, flow -20°C324 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.

Determines electrical infrastructure and whether the unit can be installed at the site.

Source
“Power supply (3 Phase) 460V 3~ 60Hz”
Installation

External branch circuit protection per UL 489 must be provided by the installer.

Affects electrical panel design and compliance before commissioning.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices drawing less than 63 A are supplied with cable but no plug, so a suitable plug/disconnect must be field-provided.

Impacts electrical connection planning and bill of materials.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Cooling water inlet must be between 5 °C and 20 °C, and pipes must be insulated if water temperature can fall below the condensation point.

Defines cooling water supply requirements and condensation/insulation measures.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so water quality must be compatible.

Guides cooling water quality and material compatibility to avoid corrosion or fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

Cooling water pressure must be at least 1 bar differential and no more than 6 bar.

Ensures adequate flow and prevents overpressure damage to the water circuit.

Source
“min. cooling water differential pressure 1 bar”
Performance

Cooling capacity drops as cooling water temperature rises, and required cooling water flow may increase.

Affects sizing of the cooling water supply and expected performance at site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Cumplimiento

Voltage and frequency tolerances are ±5% and ±2% respectively, but certain combinations (e.g., -5% voltage with +2% frequency) are not allowed.

Prevents operation outside allowed supply quality and avoids invalid tolerance combinations.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Cumplimiento

The unit is EMC Class A Group 1, which may require additional measures in residential or sensitive environments.

Informs EMC planning and potential restrictions on installation location.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety

The refrigerant is R-449A with GHS classification H280 (pressurized gas), so handling and ventilation precautions apply.

Relevant for safety assessments, refrigerant handling, and leak response planning.

Source
“R-449A (A1, H280)”
Selection

The unit is intended for externally closed applications, which constrains the hydraulic circuit design.

Ensures the chiller is applied only in compatible closed-loop external circuits.

Source
“For externally closed applications.”
Selection

The pump provides high discharge pressure (max 5.3 bar) for applications with high pressure drops.

Helps match pump capability to external circuit pressure loss.

Source
“Circulating pumps with a high discharge pressure for applications with high pressure drops.”
Operation

Ambient temperature must remain between 5 °C and 40 °C for proper operation.

Defines the allowable installation environment and ventilation/cooling needs.

Source
“min. ambient temperature 5 °C”
Maintenance

The expansion tank is atmospheric open and has a digital level indicator, so level monitoring and maintenance access are needed.

Affects routine maintenance and fluid level checks.

Source
“Housing, atmospheric open expansion tank and copper soldered evaporator made of stainless steel. With digital level indicator.”