Product introduction and main features of the circulator
Specpp. 1-2
Technical data, performance figures and operating limits
Specp. 2
Detailed parameters according to DIN 12876 standard
p. 2table, 25 rows
p. 1table, 27 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
620 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,2 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
440 kg
Power supply requirement
400V 3~ 50Hz
max. current
31,5 A
Fuse
3x32A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S588653
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Order-No.
5004.0001.01
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
12 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
14 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
10 kW
at -20°C
5 kW
at -30°C
2,1 kW
at -40°C
0,8 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
2,9 kg
CO2 equivalent
6,2 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is purpose-built for automotive applications using water-glycol mixtures down to -45°C, so it should be selected only for that fluid class.
Confirms the intended heat transfer fluid and low-temperature limit before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be kept between 5°C and 20°C, and pipes must be insulated if condensation can occur.
Defines the required facility cooling water conditions and condensation protection at the installation site.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must stay within 1 to 4 bar and static pressure must not exceed 6 bar.
Sets the allowable cooling water circuit pressure window for safe and correct operation.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 400 V three-phase 50 Hz supply with 31.5 A max current and 3x32 A fusing.
Needed to size the electrical feed, protection and connection before installation.
Source
“Power supply requirement 400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site.
Prevents surprises during commissioning regarding the missing mains plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances are ±5% and ±2% but must not combine in the unfavorable direction.
Guides assessment of site power quality before connecting the unit.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
Leakage current exceeds 3.5 mA, which affects residual current device selection and earthing requirements.
Important for electrical safety design and RCD compatibility at installation.
Source
“Attention: leakage current > 3,5mA”
Safety
The refrigerant R-452A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation must be planned.
Informs safety measures and labeling for the refrigerant circuit.
Source
“R-452A (A1, H280)”
Cumplimiento
The unit is EMC Class A Group 1, so it is intended for industrial environments and may cause interference in residential areas.
Determines EMC environment suitability and possible filtering needs.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation
Ambient temperature must remain between 5°C and 40°C for correct operation.
Defines the allowable room conditions where the unit can be operated.
Source
“min. ambient temperature 5 °C”
Operation
Cooling power drops as temperature falls, from 14 kW at 20°C to 0.8 kW at -40°C, so low-temperature duty must be checked.
Critical for verifying sufficient cooling capacity at the intended process temperature.
Source
“at -40°C 0,8 kW”
Operation
The pump delivers 201 l/min max with 5.3 bar max pressure, and flow falls with rising pressure.
Used to match the external circuit pressure drop and required flow rate.
Source
“max. delivery pressure 5,3 bar”
Maintenance
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality should be used.
Guides water treatment and material compatibility to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Pump connections are M38x1.5 male and cooling water connections are G3/4 male, so matching hoses and fittings are required.
Needed to procure correct adapters and hoses for piping.