Introduces the Unimotive 26w-XT unit and its main features
Specpp. 1-2
Operating data, temperatures, capacities and dimensions per DIN 12876
p. 2table, 22 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
1260 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/23
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
28 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
25 kW
at -20°C
14,5 kW
at -30°C
6,5 kW
at -40°C
2,6 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
3,6 kg
CO2 equivalent
7,7 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
12 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.
Determines the permissible heat transfer fluid and prevents unsuitable fluids from being specified.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be between 5°C and 20°C, and pipes must be insulated if condensation can occur.
Defines the required cooling water supply conditions and condensation protection for installation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must stay between 1 bar and 4 bar, with a maximum cooling water pressure of 6 bar.
Sets the cooling water circuit pressure limits for correct and safe connection.
Source
“min. cooling water differential pressure 1 bar”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides cooling water quality and material compatibility to avoid corrosion or damage.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and the combination -5% voltage with +2% frequency is not allowed.
Defines acceptable power supply tolerances and a prohibited voltage/frequency combination.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
Leakage current exceeds 3.5 mA, which must be considered for protective earthing and RCD selection.
Affects electrical installation and protective device selection.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be provided on site.
Determines what electrical termination is included and what must be supplied during installation.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The unit requires 400 V 3~ 50 Hz supply and has IP20 protection, so it must be installed in a dry indoor environment.
Defines the electrical supply and environmental protection required for installation.
Source
“Power supply requirement 400V 3~ 50Hz”
Operation
Ambient temperature must remain between 5°C and 40°C for operation.
Sets the permissible ambient conditions for reliable operation.
Source
“min. ambient temperature 5 °C”
Performance
Cooling power drops as temperature decreases, from 28 kW at 20°C to 2.6 kW at -40°C, which must be considered for low-temperature applications.
Allows correct sizing of cooling capacity at the required operating temperature.
Source
“at -40°C 2,6 kW”
Performance
Pump delivery decreases with increasing pressure, from 201 l/min maximum to 42 l/min at 5.0 bar.
Needed to match pump performance to the external circuit pressure drop.
Source
“Delivery at 5,0 bar 42 l/min”
Cumplimiento
The equipment is classified as EN55011 Class A Group 1, which has implications for electromagnetic compatibility in the installation environment.
Determines EMC classification and suitability for the intended electromagnetic environment.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”