Introduces the Unimotive GL 30w-XT unit and its main features
Specp. 2
Lists technical data according to DIN 12876 standard
p. 2table, 25 rows
p. 1table, 27 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
3100 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Net weight
900 kg
Power supply requirement
460V 3~ 60Hz
max. current
62,5 A
Fuse
3x63A
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/23
** Please respect space requirements. See operating conditions at www.huber-online.com
Unimotive GL 30w-XT — Technical data according to DIN 12876
Parameter
Value
Order-No.
5009.0004.01
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
35 kW
at -20°C
22 kW
at -30°C
14 kW
at -40°C
8,5 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Refrigerant quantity
9 kg
CO2 equivalent
0,0 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.
Determines compatible heat transfer fluid and achievable low-temperature range for automotive test applications.
Source
“constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C”
Installation
The cooling water inlet temperature must be between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Cooling water supply conditions must be verified on site before installation to avoid condensation and performance loss.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
The cooling water circuit requires a differential pressure between 1 bar and 4 bar and a maximum pressure of 6 bar.
The facility cooling water system must be sized to provide adequate differential pressure without exceeding the maximum.
Source
“min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar”
Installation
The unit requires a 460V 3~ 60Hz supply with a maximum current of 62.5 A and a 3x63A fuse.
Electrical supply and branch protection must be planned to match this rating before installation.
Source
“Power supply requirement
460V 3~ 60Hz
max. current
62,5 A
Fuse
3x63A”
Installation
External branch circuit protection according to UL 489 is required.
The installer must provide UL 489 listed branch protection to meet compliance.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices with current consumption less than 63A are delivered with cable but without plug.
The site must supply and install a suitable plug or hard-wired connection.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Supply quality must be checked to avoid invalid voltage/frequency combinations that could damage the unit.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.
Performance at higher cooling water temperatures must be accounted for in process design.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.
Fluid selection must respect this viscosity limit to ensure proper pump operation.
Source
“max. permissible kin. viscosity
200 mm²/s”
Safety
The unit has adjustable overtemperature protection according to DIN 12876.
Safety settings must be configured for the application to protect the process and equipment.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Safety
The refrigerant is R-744 (A1, H280) with a GWP of 1 and a charge of 9 kg.
Refrigerant safety classification and charge affect handling, ventilation, and environmental compliance.
Source
“Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)”
Maintenance
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used.
Cooling water quality must be compatible with these materials to prevent corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento
The equipment is classified as EN55011 Class A, Group 1 for electromagnetic compatibility.
Class A equipment may require additional EMC measures in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection
The unit is IP20 rated and must operate in ambient temperatures between 5°C and 40°C.
Installation location must meet the ambient temperature range and protection degree requirements.
Source
“Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C”