Contenido

  1. Overview p. 1
    Product introduction and general description of the unit
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 22 rows
  4. p. 1 table, 24 rows

Technical data according to DIN 12876

ParameterValue
max. delivery pressure5,3 bar
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure12 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unimotive GL 60w-XT (Order-No.: 5034.0002.01)

ParameterValue
Operating temperature range-45...150 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationI / NFL
Heating power48 kW
Cooling power with Water/ Glysantin 40/60 at 20°C56 kW
Cooling power with Water/ Glysantin 40/60 at 0°C48 kW
at -20°C34 kW
at -30°C27 kW
at -40°C18 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
UN-numberUN 2857
Circulation pump:MK pump
max. delivery201 l/min

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is intended for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than general lab use.

Confirms the heat transfer fluid and application envelope before specifying the circulator.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

The cooling water supply must be between 5°C and 20°C and provide at least 1 bar differential pressure, which dictates the facility water system design.

Cooling water outside this range reduces cooling capacity or requires additional infrastructure.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water falls below the condensation point, the cooling water pipes inside the unit must be insulated to prevent condensation.

Prevents condensation damage and electrical risk in low-temperature cooling water operation.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling power is rated at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure, so actual capacity will differ if site conditions deviate.

Needed to compare quoted cooling capacity against real plant conditions.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Incompatible water chemistry can corrode or degrade wetted materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed.

Defines acceptable site power quality for warranty and reliable operation.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices below 63A are supplied with cable but without plug, so the customer must provide a suitable plug and connection.

Affects electrical installation planning and scope of supply.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Three-phase devices above 63A are supplied without cable and without plug, requiring full customer-side power cabling.

Major installation cost and responsibility item for high-power units.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Installation

Pump connections use M38x1.5 male threads with bore shape Y (60°) per DIN 3863, and mating hoses need ball socket per DIN 3863 and sleeve nut per DIN 3870.

Ensures correct fittings and leak-free hose connections are ordered.

Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation

Maximum permissible kinematic viscosity of the thermal fluid is 200 mm²/s, limiting fluid choice at low temperatures.

Prevents pump overload and poor circulation with viscous fluids.

Source
“max. permissible kin. viscosity”
Safety

Maximum system pressure is 12 bar, so the external circuit and expansion vessel must be rated accordingly.

Defines pressure rating required for connected pipework and components.

Source
“max. System pressure”
Installation

The unit requires 400V 3~ 50Hz supply, which must be confirmed at the installation site.

Electrical supply mismatch prevents commissioning.

Source
“Power supply requirement”
Operation

Ambient temperature must stay between 5°C and 40°C for specified operation.

Out-of-range ambient conditions affect performance and reliability.

Source
“min. ambient temperature”
Selection

The unit is water-cooled with natural refrigerant R-744 (GWP 1), which matters for refrigerant regulations and environmental compliance.

Low-GWP refrigerant simplifies compliance and future-proofs selection.

Source
“Refrigeration machine”