Product introduction and general description of the Unistat 530w unit
Specpp. 1-2
Technical data, performance figures and operating limits per DIN 12876
p. 2table, 21 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
890 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,2 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
443 kg
sound pressure level +/- 4 dB(A)
59 dB(A)
Power supply requirement
460V 3~ 60Hz
max. current
25 A
Fuse
3x25A
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S611236
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unistat 530w (Order-No.: 5002.0102.01)
Characteristic
Value
Operating temperature range
-55...250 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
12 kW
Cooling power with Thermooil at 250°C
21 kW
Cooling power with Thermooil at 200°C
21 kW
Cooling power with Thermooil at 100°C
21 kW
Cooling power with Thermooil at 20°C
21 kW
Cooling power with Ethanol at 0°C
16 kW
Cooling power with Ethanol at -20°C
9 kW
Cooling power with Ethanol at -40°C
3 kW
Cooling power with Ethanol at -50°C
1 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-1270 (A3, H220)
Global Warming Potential (GWP)
0
Refrigerant quantity
1,35 kg
CO2 equivalent
0,0 t
Circulation pump:
MK pump
max. delivery
196 l/min
max. delivery pressure
2,5 bar
Delivery at 0,5 bar
175 l/min
Delivery at 1,0 bar
152 l/min
Delivery at 1,5 bar
123 l/min
Delivery at 2,0 bar
86 l/min
Engineering Facts
13 facts · every claim linked to a page
Installation
The unit requires a 460 V 3-phase 60 Hz supply with a 25 A max current and 3x25 A fusing, so the site electrical infrastructure must be sized accordingly.
Determines breaker, cable and panel requirements before ordering.
Source
“Power supply requirement 460V 3~ 60Hz max. current 25 A Fuse 3x25A”
Installation
Cooling water must be supplied at 5–20 °C with 1–4 bar differential pressure and max 6 bar pressure, so the facility water system must meet these limits.
Cooling water conditions directly affect cooling capacity and safe operation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature can fall below the dew point, the cooling water pipes inside the unit must be insulated to prevent condensation.
Prevents condensation damage and electrical risk in low-temperature water supply conditions.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling capacity is rated at 21 kW with Thermooil from 20 to 250 °C but drops with ethanol to 1 kW at -50 °C, so fluid choice strongly affects low-temperature performance.
Needed to verify the unit can handle the required heat load at the target process temperature.
Source
“Cooling power with Ethanol at 0°C 16 kW at -20°C 9 kW at -40°C 3 kW at -50°C 1 kW”
Performance
The magnetic-coupled stainless steel pump delivers 196 l/min max and 2.5 bar max, with 86 l/min still available at 2.0 bar, so external circuit pressure drop must be checked.
Ensures adequate flow through the external application at its actual pressure drop.
Source
“max. delivery 196 l/min max. delivery pressure 2,5 bar Delivery at 2,0 bar 86 l/min”
Safety
The refrigerant is R-1270 (A3, H220) with GWP 0 and 1.35 kg charge, so A3 flammability rules and ventilation/ignition-source precautions apply.
A3 refrigerant classification drives room ventilation, ignition-source and handling requirements.
Source
“Refrigerant (ASHRAE, GHS) R-1270 (A3, H220)”
Safety
Leakage current exceeds 3.5 mA and external branch circuit protection per UL 489 is required, so a suitable upstream breaker must be installed.
Affects electrical protection design and compliance with UL installation requirements.
Source
“Attention: leakage current > 3,5mA External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices under 63 A are supplied with cable but without a plug, so the customer must provide the final connection.
Prevents delays at commissioning due to missing plug or hardwiring provisions.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances are ±5% and ±2% but must not combine in the same direction, so supply quality must be verified.
Non-compliant supply combinations can damage the compressor and electronics.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The unit is rated for ambient temperatures of 5–40 °C and IP20 protection, so it must be installed indoors in a dry, ventilated location.
Ambient limits affect reliability and cooling performance; IP20 excludes wet or dusty environments.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection
The unit has a -55 to 250 °C operating range with 0.01 K stability and Pt100 sensors, suitable for precise external closed or open applications.
Confirms the unit meets the required process temperature window and precision.
Source
“Operating temperature range -55...250 °C Temperature stability at -10°C 0,01 K”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Incompatible water chemistry can corrode or foul the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
The unit weighs 443 kg and measures 730x804x1738 mm, so floor loading and access route must be planned.
Affects rigging, doorway clearance and structural floor requirements.
Source
“Overall dimensions WxDxH ** 730x804x1738 mm Net weight 443 kg”