Introduces the Unistat 540w unit and its main features
Specpp. 1-2
Performance, temperature, and dimensional data per DIN 12876
p. 2table, 20 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
1480 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
9,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
472 kg
Power supply requirement
400V 3~ 50Hz
max. current
55 A
Fuse
3x63A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S548344
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Characteristic
Value
Operating temperature range
-55...250 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Thermooil at 250°C
30 kW
Cooling power with Thermooil at 200°C
30 kW
Cooling power with Thermooil at 100°C
30 kW
Cooling power with Thermooil at 20°C
30 kW
Cooling power with Ethanol at 0°C
30 kW
Cooling power with Ethanol at -20°C
16 kW
Cooling power with Ethanol at -40°C
4 kW
Cooling power with Ethanol at -50°C
1,5 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
3,6 kg
CO2 equivalent
7,7 t
Circulation pump:
MK pump
max. delivery
196 l/min
max. delivery pressure
2,5 bar
Delivery at 0,5 bar
175 l/min
Delivery at 1,0 bar
152 l/min
Delivery at 1,5 bar
123 l/min
Delivery at 2,0 bar
86 l/min
Engineering Facts
13 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase supply with a 3x63 A fuse and draws up to 55 A, so the electrical installation must be sized accordingly.
Determines the site power supply, cable cross-section and protection device needed before installation.
Source
“Power supply requirement 400V 3~ 50Hz max. current 55 A Fuse 3x63A”
Installation
The cooling water circuit must be supplied at 1–4 bar differential pressure and no more than 6 bar, with 1480 l/h consumption at 15 °C water and 0 °C flow.
Sizing of the cooling water supply, pump and piping depends on these pressure and flow limits.
Source
“Consumption at water 15°C, flow 0°C 1480 l/h min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Operation
The unit is designed for cooling water intake between 5 °C and 20 °C, and cooling power drops as the water temperature rises.
The available cooling capacity and reliable operation depend on keeping the cooling water within this range.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion/electrical risk when cold cooling water is used.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Water quality must be matched to these materials to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Cumplimiento
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.
The site power quality must be checked against these combined tolerances before commissioning.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
The equipment has a leakage current greater than 3.5 mA, which affects the choice of residual current protection.
RCD selection and earthing design must account for the high leakage current.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.
The electrical installer must supply and fit the appropriate plug for commissioning.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The pump connection is M38x1.5 male with bore shape Y (60°) per DIN 3863, and pipework must use ball sockets per DIN 3863 and sleeve nuts per DIN 3870.
Ensures the correct mating fittings and hoses are procured for leak-free connection.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Selection
The unit uses refrigerant R-452A with GWP 2141 and a charge of 3.6 kg, giving a CO2 equivalent of 7.7 t.
Relevant for refrigerant regulations, leak monitoring and environmental reporting.
Source
“Refrigerant (ASHRAE, GHS) R-452A (A1, H280) Global Warming Potential (GWP) 2141 Refrigerant quantity 3,6 kg CO2 equivalent 7,7 t”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.
Limits the choice of heat transfer fluid and ensures adequate pump performance.
Source
“max. permissible kin. viscosity 100 mm²/s”
Installation
The unit has protection degree IP20 and must be operated between 5 °C and 40 °C ambient temperature.
Defines the permissible installation environment and ventilation requirements.
Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection
The unit is water-cooled and uses a CFC- and HCFC-free refrigeration machine.
Confirms the cooling medium and refrigerant compliance for selection.
Source
“Refrigeration machine water-cooled, CFC- and HCFC-free”