Product introduction and general description of the Unistat GL 550w unit
Specpp. 1-2
Technical performance data, dimensions, and operating parameters
Specp. 2
Detailed specifications according to DIN 12876 standard
p. 2table, 20 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
3100 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Net weight
800 kg
Power supply requirement
400V 3~ 50Hz
max. current
61,5 A
Fuse
3x63A
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S581643
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Characteristic
Value
Operating temperature range
-50...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Thermooil at 200°C
41 kW
Cooling power with Thermooil at 100°C
41 kW
Cooling power with Thermooil at 20°C
41 kW
Cooling power with Ethanol at 0°C
37 kW
Cooling power with Ethanol at -20°C
22 kW
Cooling power with Ethanol at -40°C
10 kW
Cooling power with Ethanol at -50°C
6 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Refrigerant quantity
8,7 kg
CO2 equivalent
0,0 t
UN-number
UN 2857
Circulation pump: MK pump
max. delivery
196 l/min
max. delivery pressure
2,5 bar
Delivery at 0,5 bar
175 l/min
Delivery at 1,0 bar
152 l/min
Delivery at 1,5 bar
123 l/min
Delivery at 2,0 bar
86 l/min
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase supply with a 3x63 A fuse and draws up to 61.5 A, so the site electrical infrastructure must be sized accordingly.
Determines the electrical supply, cable and protection device needed before installation.
Source
“Power supply requirement 400V 3~ 50Hz max. current 61,5 A Fuse 3x63A”
Installation
The cooling water circuit must be supplied at 5–20 °C with 1–4 bar differential pressure and no more than 6 bar pressure, and pipes must be insulated if water can drop below the dew point.
Defines the cooling water utility requirements and condensation risk at the installation site.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
The cooling water connection is G3/4 male and the pump connection is M38x1.5 male, so matching hoses and adapters must be procured.
Needed to order correct hoses, fittings and adapters for commissioning.
Source
“Pump connection M38x1,5 male”
Installation
The unit is 918x963x1771 mm and weighs 800 kg, so transport routes, floor loading and clearance must be planned.
Affects rigging, doorway clearance and structural floor requirements.
Source
“Overall dimensions WxDxH ** 918x963x1771 mm Net weight 800 kg”
Installation
The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient, so it cannot be installed in a wet or condensing environment.
Constrains the installation location regarding moisture and ambient temperature.
Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Safety
The equipment produces leakage current above 3.5 mA, which requires appropriate protective earthing and RCD selection.
Affects electrical protection design and compliance with local wiring regulations.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so a suitable plug must be supplied on site.
Prevents commissioning delays because the customer must provide the plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Cumplimiento
Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.
Must be checked against the site power quality to avoid invalid operating conditions.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The unit uses R-744 (CO2) refrigerant with GWP 1 and a charge of 8.7 kg, which simplifies refrigerant regulations compared with high-GWP fluids.
Relevant for environmental compliance and refrigerant handling requirements.
Cooling capacity depends strongly on the heat transfer fluid and temperature, e.g. 41 kW with thermooil at 20–200 °C but only 6 kW with ethanol at -50 °C.
Needed to verify the unit meets the process heat load at the required operating temperature.
Source
“Cooling power with Ethanol at -50°C 6 kW”
Performance
The circulation pump delivers 196 l/min maximum and 86 l/min at 2.0 bar, so system pressure drop must be checked against the pump curve.
Ensures adequate flow through the external circuit at the actual pressure drop.
Source
“max. delivery 196 l/min max. delivery pressure 2,5 bar Delivery at 2,0 bar 86 l/min”
Operation
Minimum filling capacity is 8.9 l and the expansion tank holds 19.9 l, which sets the heat transfer fluid charge and expansion allowance.
Determines fluid volume to purchase and expansion volume available.
Source
“min. filling capacity 8,9 l Filling capacity expansion tank 19,9 l”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and treatment to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento
The unit is EMC classified as Class A, Group 1 to EN55011, which may require additional filtering in residential or sensitive environments.
Affects EMC planning and suitability for the intended electromagnetic environment.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”