Introduces the Unistat P635w unit and its main features
Specpp. 1-2
Lists performance, temperature, and physical specifications per DIN 12876
p. 2table, 17 rows
p. 1table, 31 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Characteristic
Unistat P635w
Order-No.
5019.0101.01
Operating temperature range
-60...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Thermooil at 200°C
27 kW
Cooling power with Thermooil at 100°C
27 kW
Cooling power with Thermooil at 20°C
27 kW
Cooling power with Ethanol at 0°C
27 kW
Cooling power with Ethanol at -20°C
25 kW
Cooling power with Ethanol at -40°C
14 kW
Cooling power with Ethanol at -60°C
3,5 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Circulation pump
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase supply and must be hard-wired without a plug because its current exceeds 63 A.
Determines electrical supply design, cable sizing and whether a plug/socket is needed at the installation site.
Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Installation
Cooling water must be supplied at 1–4 bar differential pressure and no more than 6 bar static pressure, with inlet temperature between 5 °C and 20 °C.
Defines the facility cooling-water loop requirements and protects the water-cooled refrigeration circuit.
Source
“min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar”
Installation
If cooling water is colder than the condensation point, the cooling water pipes inside the unit must be insulated.
Prevents condensation, corrosion and electrical risk when using cold facility water.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling capacity is rated at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, and drops as cooling water temperature rises.
Allows correct comparison of quoted cooling power against actual site conditions.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation
Voltage and frequency tolerances are ±5 % and ±2 % respectively, but the combination of −5 % voltage with +2 % frequency is not permitted.
Guides power quality assessment and generator/UPS compatibility checks.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
The unit is classified as pressure equipment category I and has safety classification III / FL according to DIN 12876.
Relevant for risk assessment, permissible fluids and compliance documentation.
Source
“Safety classification
III / FL”
Safety
The refrigerant R-452A is classified A1 with GHS hazard H280, and has a GWP of 2141.
Affects refrigerant handling, leak detection, F-gas reporting and environmental compliance.
Source
“R-452A (A1, H280)”
Operation
The pump delivers 201 l/min maximum and 42 l/min at 5.0 bar, with a maximum delivery pressure of 5.3 bar.
Needed to match the circulator to external circuit pressure drop and required flow.