Product introduction and general description of the Unistat P640w unit
Specpp. 1-2
Technical specifications and performance data according to DIN 12876
p. 2table, 17 rows
p. 1table, 29 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unistat P640w (Order-No.: 5020.0101.01)
Characteristic
Value
Operating temperature range
-60...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Thermooil at 200°C
32 kW
Cooling power with Thermooil at 100°C
32 kW
Cooling power with Thermooil at 20°C
35 kW
Cooling power with Ethanol at 0°C
35 kW
Cooling power with Ethanol at -20°C
30 kW
Cooling power with Ethanol at -40°C
14 kW
Cooling power with Ethanol at -60°C
3,5 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Circulation pump: MK pump max. delivery
201 l/min
Circulation pump: MK pump max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Значения приведены дословно; строки охлаждения сведены по параметру (теплоноситель/температура) в одну колонку характеристик.
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase 50 Hz supply, so the electrical infrastructure must be verified before installation.
Determines the mains connection, cabling and protection needed at the installation site.
Source
“Power supply requirement
400V 3~ 50Hz”
Installation
The cooling water supply must be kept between 5 °C and 20 °C inlet temperature for the stated performance.
Cooling water temperature directly affects achievable cooling power and must be planned for.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water pipes must be insulated if the water temperature can drop below the condensation point.
Prevents condensation and corrosion damage in the cooling water circuit.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
The cooling water circuit requires a differential pressure between 1 and 4 bar and must not exceed 6 bar.
Defines the required cooling water supply pressure and protects the unit from overpressure.
Source
“min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar”
Installation
Three-phase devices drawing less than 63 A are supplied with a cable but without a plug.
The customer must provide and fit the appropriate plug/connection on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The pump connection is M38x1.5 male and must mate with ball-socket fittings per DIN 3863 and sleeve nuts per DIN 3870.
Ensures correct selection of hoses and fittings for the external circuit.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Installation
The unit needs sufficient space around its 918x963x1771 mm footprint and must be installed in an ambient range of 5–40 °C.
Space and ambient conditions affect access, ventilation and reliable operation.
Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Operation
The pump delivers 201 l/min max and 5.3 bar max, dropping to 42 l/min at 5.0 bar, so high-pressure-drop loops must be checked against the curve.
Confirms whether the pump can overcome the pressure drop of the external application.