Unichiller 070Tw-H Datasheet

Sommaire

  1. Overview p. 1
    Product introduction and main features of the chiller
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 17 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Consumption at water 15°C, flow 15°C474 l/h
Consumption at water 15°C, flow 0°C330 l/h
Consumption at water 15°C, flow -10°C264 l/h
min. cooling water differential pressure1,5 bar
max. cooling water pressure6 bar
min. filling capacity5,9 l
Volume of expansion7,5 l
Overall dimensions WxDxH **600x600x1450 mm
Net weight212 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)12 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S561183

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 070Tw-H (Order-No.: 3016.0032.01)

ParameterValue
Operating temperature range-10...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C7 kW
Cooling power at 0°C4,2 kW
Cooling power at -10°C2,5 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,35 kg
CO2 equivalent1,9 t
Circulation pumpC3
max. delivery84 l/min
max. delivery pressure5,6 bar
Delivery at 0,33 bar81 l/min
Delivery at 0,5 bar79 l/min
Delivery at 1,0 bar74 l/min
Delivery at 1,5 bar69 l/min
Delivery at 2,0 bar64 l/min
Delivery at 2,5 bar58 l/min
Delivery at 3,0 bar52 l/min
Delivery at 3,5 bar46 l/min
Delivery at 4,0 bar39 l/min
Delivery at 4,5 bar30 l/min
Delivery at 5,0 bar21 l/min
Delivery at 5,5 bar7 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller requires a three-phase 400 V supply with a 3x16 A fuse, so the electrical installation must be sized accordingly.

Determines the mains connection, cable and protection device needed at the installation site.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

The unit is water-cooled and needs a cooling water supply with at least 1.5 bar differential pressure and no more than 6 bar.

Cooling water pressure must be verified before installation to ensure sufficient flow and avoid overpressure damage.

Source
“min. cooling water differential pressure 1,5 bar”
Installation

Cooling water inlet temperature must be kept between 5 °C and 20 °C, and pipes must be insulated if below the condensation point.

Out-of-range cooling water temperature affects cooling capacity and can cause condensation and corrosion.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops significantly as the working temperature decreases, from 7 kW at 15 °C to 2.5 kW at -10 °C.

Process heat load must be matched to the available cooling capacity at the actual operating temperature.

Source
“at 15°C 7 kW”
Performance

The circulation pump delivers 84 l/min maximum, but flow falls sharply at higher pressure, down to 7 l/min at 5.5 bar.

External circuit pressure drop must be checked against the pump curve to ensure adequate flow.

Source
“max. delivery 84 l/min”
Safety

The refrigerant R-449A is classified A1 with GHS hazard H280, and the charge is 1.35 kg with a CO2 equivalent of 1.9 t.

Refrigerant safety class and charge affect room ventilation, leak detection and environmental reporting obligations.

Source
“R-449A (A1, H280)”
Operation

The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient temperature.

Ambient conditions in the installation room must be controlled to avoid overheating or condensation.

Source
“max. ambient temperature 40 °C”
Installation

The chiller is intended for externally closed applications and has an atmospheric open expansion tank.

The hydraulic circuit must be designed as a closed loop; open baths or unsealed circuits are not suitable.

Source
“For externally closed applications.”
Conformité

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Site power quality must be checked to avoid invalid supply combinations that could damage the unit.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices below 63 A are supplied with cable but without a plug, so a suitable plug must be provided on site.

The electrical installer must plan for a matching plug and socket, not assume a ready-to-plug unit.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality may be used.

Water chemistry must be compatible with these materials to prevent corrosion and fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection

The unit has a minimum filling capacity of 5.9 l and an expansion volume of 7.5 l, which sets the minimum external circuit volume.

External loop volume and expansion must be considered when selecting and commissioning the system.

Source
“min. filling capacity 5,9 l”