Unichiller 110Tw-H Technical Datasheet

Sommaire

  1. Overview p. 1
    Product name and general description of the chiller unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating parameters per DIN 12876
  3. p. 2 table, 17 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 15°C400 l/h
Consumption at water 15°C, flow 0°C191 l/h
Consumption at water 15°C, flow -10°C89 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity6,5 l
Volume of expansion5,5 l
Overall dimensions WxDxH **600x600x1450 mm
Net weight372 kg
sound pressure level +/- 4 dB(A)65 dB(A)
Power supply (3 Phase)460V 3~ 60Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/21

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

CharacteristicUnichiller 110Tw-H
Order-No.3027.0069.01
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C11 kW
Cooling power at 0°C6 kW
Cooling power at -10°C2,7 kW
Cooling power at -20°C2 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
UN-numberUN 2857
Circulation pumpC3
max. delivery97 l/min
max. delivery pressure6,5 bar
Delivery at 0,35 bar108 l/min
Delivery at 0,5 bar106 l/min
Delivery at 1,0 bar101 l/min
Delivery at 1,5 bar96 l/min
Delivery at 2,0 bar90 l/min
Delivery at 2,5 bar84 l/min
Delivery at 3,0 bar78 l/min
Delivery at 3,5 bar71 l/min
Delivery at 4,0 bar64 l/min
Delivery at 4,5 bar56 l/min
Delivery at 5,0 bar48 l/min
Delivery at 5,5 bar38 l/min
Delivery at 6,0 bar24 l/min
Pump connectionG1 1/4 male

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.

Electrical supply must match before ordering and installation.

Source
“Power supply (3 Phase) 460V 3~ 60Hz”
Installation

The unit is water-cooled and needs cooling water connections of G3/4 male with a minimum differential pressure of 1 bar.

Cooling water piping and pressure must be planned for installation.

Source
“Cooling water connection G3/4 male”
Installation

Cooling water pressure must not exceed 6 bar, so a pressure reducer may be required.

Prevents overpressure damage to the cooling water circuit.

Source
“max. cooling water pressure 6 bar”
Operation

The unit is designed for cooling water intake between 5°C and 20°C, and lower temperatures require insulating the cooling water pipes.

Operating outside this range or without insulation can cause condensation issues.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.

Performance must be derated if site cooling water is warmer than 15°C.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water should be used.

Water quality must be compatible to avoid corrosion or damage.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed.

Site power quality must be checked against these limits.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety

External branch circuit protection according to UL 489 is required.

Electrical installation must include UL 489 branch protection.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without plug.

The installer must provide a suitable plug or hardwiring.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The unit must be operated within an ambient temperature range of 5°C to 40°C.

Ambient conditions affect reliable operation and must be verified.

Source
“min. ambient temperature 5 °C”
Safety

The refrigerant is R-449A with GHS classification A1, H280, and UN number UN 2857.

Refrigerant safety data must be known for handling and emergency planning.

Source
“R-449A (A1, H280)”
Maintenance

The unit has a minimum filling capacity of 6.5 l and expansion volume of 5.5 l.

Heat transfer fluid volume must be planned for commissioning and maintenance.

Source
“min. filling capacity 6,5 l”
Installation

The unit weighs 372 kg net, so floor loading and lifting equipment must be considered.

Installation site must support the weight and allow safe handling.

Source
“Net weight 372 kg”
Operation

The circulation pump delivers up to 97 l/min and 6.5 bar, with flow decreasing at higher pressure.

External circuit pressure drop must be matched to the pump curve.

Source
“max. delivery 97 l/min”