Introduces the Unichiller 160Tw-H chiller and its main features
Specpp. 1-2
Performance, temperature, cooling capacity and dimensional data per DIN 12876
p. 2table, 18 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
Consumption at water 15°C, flow 15°C
600 l/h
Consumption at water 15°C, flow 0°C
320 l/h
Consumption at water 15°C, flow -10°C
133 l/h
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
min. filling capacity
6,5 l
Volume of expansion
10 l
Overall dimensions WxDxH **
600x600x1450 mm
Net weight
233 kg
sound pressure level +/- 4 dB(A)
65 dB(A)
Power supply (3 Phase)
400V 3~ 50Hz
max. current (3 Phase)
17 A
Fuse (3 phase)
3x20A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S612165
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unichiller 160Tw-H (Order-No.: 3056.0005.01)
Parameter
Value
Operating temperature range
-20...100 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
III / FL
Heating power
2 kW
Cooling power at 15°C
16 kW
Cooling power at 0°C
9,5 kW
Cooling power at -10°C
5,5 kW
Cooling power at -20°C
4 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
2,1 kg
CO2 equivalent
2,9 t
UN-number
UN 2857
Circulation pump
C3
max. delivery
96 l/min
max. delivery pressure
5,6 bar
Delivery at 0,5 bar
92 l/min
Delivery at 1,0 bar
86 l/min
Delivery at 1,5 bar
81 l/min
Delivery at 2,0 bar
75 l/min
Delivery at 2,5 bar
68 l/min
Delivery at 3,0 bar
62 l/min
Delivery at 3,5 bar
54 l/min
Delivery at 4,0 bar
46 l/min
Delivery at 4,5 bar
37 l/min
Delivery at 5,0 bar
24 l/min
Pump connection
G1 1/4 male
Cooling water connection
G3/4 male
Engineering Facts
14 facts · every claim linked to a page
Installation
The chiller is water-cooled and requires cooling water inlet temperature between 5°C and 20°C, so the site must provide cooling water within this range.
Cooling water temperature outside this range will affect cooling capacity and may require additional measures.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion on cooling water piping.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.
Selection must account for actual site cooling water temperature to ensure sufficient cooling capacity.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water must be used.
Incompatible water quality can cause corrosion or fouling in the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Conformité
Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.
Power supply quality must be checked to avoid invalid voltage/frequency combinations that could damage the unit.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
Three-phase devices with current consumption less than 63A are supplied with cable but without plug.
The installer must provide a suitable plug or direct connection for this 17A three-phase unit.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The unit has adjustable overtemperature protection according to DIN 12876.
Overtemperature protection must be set correctly for safe operation with external closed applications.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection
The chiller is intended for externally closed applications.
The unit is not suitable for open bath applications; the process loop must be closed.
Source
“For externally closed applications.”
Installation
The minimum cooling water differential pressure is 1 bar and maximum cooling water pressure is 6 bar.
The cooling water supply must provide at least 1 bar differential pressure and must not exceed 6 bar.
Source
“min. cooling water differential pressure 1 bar”
Operation
The unit is rated IP20, so it must be installed in an environment protected from dust and water ingress.
IP20 limits installation locations and requires protection from moisture and dust.
Source
“Degree of Protection IP20”
Operation
The ambient temperature must be between 5°C and 40°C.
Operating outside this ambient range may affect performance and reliability.
Source
“min. ambient temperature 5 °C”
Installation
The unit requires a 400V 3~ 50Hz power supply with maximum current 17A and 3x20A fuses.
Electrical supply and protection must be sized accordingly.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Maintenance
The refrigerant is R-449A with GWP 1397 and charge 2.1 kg, corresponding to 2.9 t CO2 equivalent.
Refrigerant handling and leak checks must follow applicable regulations for this charge and GWP.
Source
“Refrigerant quantity 2,1 kg”
Selection
The circulation pump delivers a maximum of 96 l/min at 5.6 bar, with delivery dropping at higher pressures.
Pump curve must be checked against the pressure drop of the external circuit to ensure required flow.