Unichiller 160Tw Technical Data

Sommaire

  1. Overview p. 1
    Introduces the Unichiller 160Tw chiller model
  2. Spec p. 2
    Technical data according to DIN 12876 standard
  3. p. 2 table, 15 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity6,5 l
Volume of expansion10 l
Overall dimensions WxDxH **600x600x1450 mm
Net weight225 kg
sound pressure level +/- 4 dB(A)65 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)12 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S545352

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 160Tw (Order-No.: 3056.0006.01)

ParameterValue
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 15°C16 kW
Cooling power at 0°C9,5 kW
Cooling power at -10°C5,5 kW
Cooling power at -20°C4 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity2,1 kg
CO2 equivalent2,9 t
Circulation pumpC3
max. delivery96 l/min
max. delivery pressure5,6 bar
Delivery at 0,5 bar92 l/min
Delivery at 1,0 bar86 l/min
Delivery at 1,5 bar81 l/min
Delivery at 2,0 bar75 l/min
Delivery at 2,5 bar68 l/min
Delivery at 3,0 bar62 l/min
Delivery at 3,5 bar54 l/min
Delivery at 4,0 bar46 l/min
Delivery at 4,5 bar37 l/min
Delivery at 5,0 bar24 l/min
Pump connectionG1 1/4 male
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 15°C600 l/h
Consumption at water 15°C, flow 0°C320 l/h
Consumption at water 15°C, flow -10°C133 l/h

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller requires cooling water inlet temperature between 5°C and 20°C, and pipes must be insulated if water temperature can fall below the condensation point.

Defines the permissible cooling water supply conditions and insulation requirement for correct installation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power ratings are valid only at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure, so actual capacity will differ under other conditions.

Prevents overestimating cooling capacity when site conditions differ from the rating basis.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Performance

Higher cooling water temperature reduces cooling power and may require increased cooling water flow rate.

Affects sizing of the cooling water supply and expected performance at the installation site.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility checks to avoid corrosion or damage.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

Cooling water pressure must be between 1 bar minimum differential and 6 bar maximum.

Sets the required cooling water supply pressure window for safe and effective operation.

Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without plug.

Requires the installer to provide a suitable plug and connection on site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Conformité

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.

Defines acceptable power supply quality and prohibited voltage/frequency combinations for compliance.

Source
“-5% voltage and +2% frequency -> not allowed!”
Safety

The unit is classified as Class A, Group 1 for electromagnetic disturbance to EN55011.

Informs EMC planning and whether additional filtering or separation may be needed.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit has protection degree IP20 and must be installed in an environment with ambient temperature between 5°C and 40°C.

Constrains the installation location regarding dust/water ingress and ambient temperature.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection

The chiller is water-cooled and uses refrigerant R-449A with GWP 1397 and a charge of 2.1 kg (2.9 t CO2 equivalent).

Relevant for refrigerant regulations, leak detection requirements and environmental compliance.

Source
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280) Global Warming Potential (GWP) 1397 Refrigerant quantity 2,1 kg CO2 equivalent 2,9 t”
Selection

The circulation pump delivers a maximum of 96 l/min and 5.6 bar, with flow dropping as pressure rises.

Used to check whether the pump can overcome the external circuit pressure drop at the required flow.

Source
“max. delivery 96 l/min max. delivery pressure 5,6 bar”
Operation

The unit is intended for externally closed applications and has an atmospheric open expansion tank.

Defines the permissible hydraulic circuit type and prevents use in open or unsuitable loops.

Source
“For externally closed applications.”
Maintenance

The minimum filling capacity is 6.5 l and the expansion volume is 10 l.

Needed to prepare the correct heat transfer fluid volume and expansion allowance.

Source
“min. filling capacity 6,5 l Volume of expansion 10 l”
Installation

The unit requires a 400V 3~ 50Hz supply with maximum current 12A and 3x16A fusing.

Determines electrical supply, cable and protection device sizing for installation.

Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current (3 Phase) 12 A Fuse (3 phase) 3x16A”