Selection
The chiller is rated for an operating temperature range of -20 to 100 °C, which defines the process window it can serve.
Confirms whether the unit covers the required process temperatures before selection.
Source
“Operating temperature range
-20...100 °C”
Performance
Cooling capacity drops sharply with lower temperature (30 kW at 15 °C down to 6 kW at -20 °C), so sizing must use the capacity at the actual setpoint.
Prevents undersizing when the process runs at low temperatures.
Source
“at 15°C
30 kW
at 0°C
18 kW
at -10°C
11 kW
at -20°C
6 kW”
Installation
The unit requires a 460 V three-phase 60 Hz supply, which dictates the site power infrastructure.
Electrical supply must match before installation planning.
Source
“Power supply (3 Phase)
460V 3~ 60Hz”
Installation
Three-phase devices under 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation scope and materials.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Conformité
External branch circuit protection per UL 489 is mandatory, so the installer must provide a listed breaker.
Required for code-compliant electrical installation.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Voltage and frequency tolerances are ±5% and ±2% but must not combine in the unfavorable direction, so supply quality must be verified.
Prevents operation outside allowed supply conditions.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Operation
Cooling capacity is valid at 20 °C room temperature and may drop at higher ambient, so the installation room must be considered.
Ambient conditions affect achievable performance.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The unit is rated IP20 and must be installed in an environment between 5 and 40 °C ambient.
Defines environmental limits and protection against ingress.
Source
“Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Safety
The refrigerant R-449A is classified A1 with GHS H280, so refrigerant handling and ventilation precautions apply.
Safety classification affects site risk assessment and handling.
Source
“R-449A (A1, H280)”
Installation
The pump connection is G1 1/4 male, so mating hoses and couplings must match this thread.
Ensures correct hydraulic connection hardware.
Source
“Pump connection
G1 1/4 male”
Selection
Minimum filling capacity is 14 l and expansion volume is 39 l, which sets the minimum loop volume and expansion allowance.
Needed to size the external circuit and expansion volume.
Source
“min. filling capacity
14 l
Volume of expansion
39 l”
Installation
Overall dimensions are 905x2172x1900 mm, so space and access must be planned accordingly.
Determines footprint and clearance requirements.
Source
“Overall dimensions WxDxH **
905x2172x1900 mm”
Conformité
The equipment is EMC Class A Group 1, which may require attention in residential-like environments.
Affects EMC compliance and installation environment.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”