Unichiller GL 035w Datasheet

Sommaire

  1. Overview p. 1
    Product introduction and model identification
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 1 table, 27 rows

Unichiller GL 035w — Technical data according to DIN 12876

CharacteristicValue
Order-No.5504.0003.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 20°C3,5 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
UN-numberUN 2857
max. delivery50 l/min
max. delivery pressure3,5 bar
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
Volume of expansion9,5 l
Overall dimensions WxDxH **550x760x1455 mm
Power supply (3 Phase)460V 3~ 60Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.1.0/26

** Technical details and dimensions are subject to change. No liability is accepted for errors or omissions. Illustrations can deviate from the original.

Engineering Facts

12 facts · every claim linked to a page
Installation

The unit requires a minimum cooling water differential pressure of 1 bar to operate correctly.

Ensures the cooling water supply has adequate pressure for proper heat rejection.

Source
“min. cooling water differential pressure 1 bar”
Installation

The maximum permissible cooling water pressure is 6 bar, so supply pressure must be regulated below this limit.

Prevents damage to the cooling water circuit components from overpressure.

Source
“max. cooling water pressure 6 bar”
Operation

The unit is designed for cooling water intake temperatures between 5°C and 20°C, and pipes must be insulated if condensation occurs.

Operating outside this range reduces cooling capacity or causes condensation issues.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.

Affects sizing of the cooling water supply and expected performance at elevated water temperatures.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality requirements to avoid corrosion or degradation of circuit materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité

Voltage tolerance is ±5% only when frequency tolerance is simultaneously ±2%, and certain combinations are not allowed.

Ensures the electrical supply stays within safe operating limits for the compressor and electronics.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

External branch circuit protection according to UL 489 is required for this equipment.

Mandatory for electrical installation compliance and safe operation in North America.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without a plug.

Installer must provide and connect a suitable plug or hardwired connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The unit has adjustable overtemperature protection according to DIN 12876 for safe operation.

Provides a safety cut-off to prevent overheating of the bath or process.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection

The refrigerant is R-744 (CO2) with GWP 1, classified A1 and H280, and the unit carries UN number 2857.

Informs refrigerant handling, safety classification, and environmental impact for selection and service.

Source
“R-744 (A1, H280)”
Operation

The ambient temperature must remain between 5°C and 40°C for proper operation.

Ensures the chiller is installed in a location with adequate ventilation and temperature control.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit has IP20 degree of protection, so it must be installed in a dry indoor environment.

Prevents ingress of water and dust that could damage electrical components.

Source
“Degree of Protection IP20”