Product introduction and general description of the unit
Specp. 2
Technical data according to DIN 12876
p. 2table, 25 rows
p. 1table, 27 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
2100 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
600 kg
Power supply requirement
460V 3~ 60Hz
max. current
47 A
Fuse
3x63A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/23
** Please respect space requirements. See operating conditions at www.huber-online.com
Unimotive GL 10w-XT — Technical data according to DIN 12876
Parameter
Value
Order-No.
5008.0004.01
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
21,5 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
17,5 kW
at -20°C
11,5 kW
at -30°C
7,5 kW
at -40°C
4,5 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Refrigerant quantity
3,3 kg
CO2 equivalent
0,0 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is purpose-built for automotive applications using water-ethylene glycol mixtures with corrosion protection down to -45°C, so it should be selected only for that fluid family.
Confirms the intended heat transfer fluid and low-temperature limit before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be kept between 5°C and 20°C, and pipes must be insulated if condensation conditions occur.
Defines the facility cooling water requirements and condensation protection needed at installation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must stay between 1 bar and 4 bar, with a maximum supply pressure of 6 bar.
Ensures the site cooling water loop can deliver adequate flow without overpressurizing the unit.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 460V 3-phase 60Hz supply with 47 A max current and 3x63A fusing, and three-phase devices under 63A ship without a plug.
Drives electrical supply sizing, branch protection, and the need to provide a suitable plug/disconnect on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Conformité
External branch circuit protection according to UL 489 is required, so the installation must include a UL 489 listed breaker.
Mandatory for compliant electrical installation in the target market.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Voltage and frequency tolerances are ±5% and ±2% respectively, but they must not combine in the unfavorable direction.
Prevents specifying a supply that exceeds the allowed combined tolerance envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
Cooling capacity drops as cooling water temperature rises and required cooling water flow may increase, so performance must be derated accordingly.
Affects achievable cooling performance and cooling water demand at the actual site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion or fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Pump connections are M38x1.5 male and cooling water connections are G3/4 male, so matching hoses and fittings must be procured.
Determines the connection hardware needed for piping and cooling water hookup.
Source
“Pump connection M38x1,5 male”
Installation
Pump connections use bore shape Y (60°) per DIN 3863 with ball socket and sleeve nut per DIN 3870, so fittings must follow these standards.
Ensures correct mating fittings for leak-free pump circuit connections.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, limiting fluid choice at low temperatures.
Prevents selecting a fluid too viscous for the pump at operating temperature.
Source
“max. permissible kin. viscosity 200 mm²/s”
Safety
The refrigerant is R-744 (A1, H280) with GWP 1 and 3.3 kg charge, so CO2 safety and ventilation measures apply.
Informs refrigerant hazard classification and environmental impact for selection and safety planning.
Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Operation
The unit has IP20 protection and must operate between 5°C and 40°C ambient, so it needs a clean, temperature-controlled indoor location.
Restricts installation environment and prevents exposure to dust and water.
Source
“Degree of Protection IP20”
Maintenance
The unit has a minimum filling capacity of 8.9 l and a 19.9 l expansion tank, so the fluid charge and expansion volume must be planned.
Sets the minimum heat transfer fluid volume and expansion allowance for commissioning.