  1. Overview p. 1
    Product introduction and general description of the Unistat P650w unit
  2. Spec pp. 1-2
    Technical performance data and operating parameters per DIN 12876
  3. p. 2 table, 19 rows
  4. p. 1 table, 29 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 5,0 bar50 l/min
Pump connectionflange DN32 PN10/40 EN1092-1
max. permissible kin. viscosity50 mm²/s
Cooling water connectionflange DN32 PN10/40 EN1092-1
Consumption at water 15°C, flow 0°C5000 l/h
min. cooling water differential pressure3 bar
max. cooling water pressure6 bar
min. filling capacity28 l
Filling capacity expansion tank28 l
Overall dimensions WxDxH **2210x1300x2160 mm
Net weight2500 kg
Power supply requirement400V 3~ 50Hz
max. current100 A
Fuse3x125A
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S486629

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat P650w (Order-No.: 1078.0003.01)

ParameterValue
Operating temperature range-60...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power48 kW
Cooling power with Thermooil at 200°C65 kW
Cooling power with Thermooil at 100°C65 kW
Cooling power with Ethanol at 0°C65 kW
Cooling power with Ethanol at -20°C56 kW
Cooling power with Ethanol at -40°C29 kW
Cooling power with Ethanol at -60°C10 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-507 (A1, H280)
Global Warming Potential (GWP)3985
Refrigerant quantity26,5 kg
CO2 equivalent105,6 t
Circulation pump: MK pump max. delivery343 l/min
max. delivery pressure5,5 bar
Delivery at 1,0 bar300 l/min
Delivery at 2,0 bar250 l/min
Delivery at 3,0 bar191 l/min
Delivery at 4,0 bar135 l/min

Значения приведены дословно; строки 'Cooling power with Thermooil' и 'Cooling power with Ethanol' в оригинале разбиты на подстроки по температурам.

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V 3~ 50 Hz supply with up to 100 A and 3x125 A fusing, so the electrical infrastructure must be sized accordingly.

Determines site power distribution, cable sizing and breaker selection before installation.

Source
“Power supply requirement 400V 3~ 50Hz max. current 100 A Fuse 3x125A”
Installation

Cooling water must be supplied at 5–20 °C with 3–6 bar differential pressure and about 5000 l/h at 15 °C, so the facility water system must meet these limits.

Cooling water capacity and pressure directly govern whether the unit can deliver rated cooling power.

Source
“Consumption at water 15°C, flow 0°C 5000 l/h min. cooling water differential pressure 3 bar max. cooling water pressure 6 bar”
Installation

Cooling water pipes must be insulated when water temperature falls below the condensation point to prevent condensation.

Prevents condensation damage and maintains reliable operation in low-temperature cooling water service.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Rated cooling power is valid only at 20 °C room temperature, 15 °C cooling water inlet and 3 bar differential pressure, so actual performance will differ outside these conditions.

Prevents overestimating cooling capacity when site conditions deviate from the rating basis.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 3 bar differential pressure between cooling water inlet and - outlet.”
Performance

Higher cooling water temperature reduces cooling power and may require increased cooling water flow, so the water system must be designed with margin.

Affects selection margin and cooling water supply design for warm climates or shared utilities.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The unit is water-cooled and uses R-507 refrigerant with 26.5 kg charge and 105.6 t CO2 equivalent, which affects refrigerant handling and environmental compliance.

Large refrigerant charge triggers F-gas record-keeping, leak checks and service planning.

Source
“Refrigerant quantity 26,5 kg CO2 equivalent 105,6 t”
Installation

Pump and cooling water connections are DN32 PN10/40 flanges to EN1092-1, so mating flanges and gaskets must be procured accordingly.

Determines pipework interface and flange hardware needed for connection.

Source
“Pump connection flange DN32 PN10/40 EN1092-1”
Installation

The unit weighs 2500 kg and measures 2210x1300x2160 mm, so floor loading, transport route and space requirements must be verified.

Needed for rigging, floor loading and room layout planning.

Source
“Overall dimensions WxDxH ** 2210x1300x2160 mm Net weight 2500 kg”
Safety

Leakage current exceeds 3.5 mA, so protective earthing and RCD selection must account for this.

Affects electrical protection design and compliance with local installation rules.

Source
“Attention: leakage current > 3,5mA”
Installation

Three-phase devices above 63 A are supplied without cable and without plug, so the customer must provide the power connection.

Requires planning and procurement of suitable cable and termination by the installer.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Operation

The unit is designed for cooling water intake between 5 °C and 20 °C, so warmer site water may require additional cooling or derating.

Defines acceptable cooling water supply temperature for warranty and performance.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

Voltage and frequency tolerances are ±5% and ±2% but not simultaneously in the unfavorable combination, so supply quality must be checked.

Ensures the electrical supply stays within the unit's allowed tolerance envelope.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Conformité

The unit is classified Class A, Group 1 for electromagnetic disturbance, so it is intended for industrial environments and may cause interference in residential areas.

Affects EMC planning and suitability of the installation location.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation

The unit has IP20 protection and must be operated between 5 °C and 40 °C ambient, so it cannot be installed in wet or hot environments.

Restricts installation location and environmental conditions.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”