Induztr
Engineering Digest Document Viewer Related Models

HTS Heat Transfer Station Operation Manual

Contents

  1. pp. 6-6
    Lists document sections and page references
  2. Overview pp. 7-7
    Explains operating principle of the heat transfer station
  3. Overview pp. 9-9
    Introduces manual purpose and manufacturer information
  4. Overview pp. 10-12
    General introduction, safety notes and intended use
  5. Spec pp. 13-15
    Specifications, dimensions and operating limits of the unit
  6. Procedure pp. 16-23
    Step-by-step commissioning procedures and checks
  7. Overview pp. 24-25
    Detailed description of components and control functions
  8. Procedure pp. 26-28
    Procedures for entering and configuring setup parameters
  9. Procedure pp. 29-29
    Instructions for everyday operation of the station
  10. Procedure pp. 30-35
    Maintenance schedules, service procedures and checks
  11. Procedure pp. 36-38
    Procedures for safe shutdown and decommissioning
  12. pp. 39-40
    Supplementary information, temperature ranges and references
  13. p. 25 table, 3 rows
  14. p. 24 table, 7 rows
  15. p. 7 table, 40 rows
  16. p. 10 table, 6 rows
  17. p. 13 table, 6 rows
  18. p. 14 table, 3 rows
  19. p. 21 table, 6 rows
  20. p. 30 table, 7 rows
  21. p. 31 table, 1 rows

Designation / Specification

DesignationSpecification
Thermal fluid: Water-ethylene glycol mixture
Use< +3 °C
Thermal fluid compositionThe mixture’s temperature must be 10 K below the permissible min. temperature. For the permissible temperature range, refer to the datasheet. → From page 39, section »Annex«.

Designation / Specification

DesignationSpecification
Calcium carbonate per liter≤ 1.5 mmol/l; corresponds to a water hardness of: ≤ 8.4 °dH (soft)
pH valuebetween 6.0 and 8.5
Ultrapure water, distillatesAdd 0.1 g of sodium carbonate (Na2CO3) per liter
Not approved waterDistilled, deionized, demineralized, chloric, ferruginous, ammoniacal, contaminated or untreated river water or sea water
Volume circulated (at least)3 l/min.
Thermal fluid: Water without ethylene glycolUse ≥ +3 °C
Thermal fluid: Water

Содержание (оглавление) страницы 7

РазделНазваниеСтраница
3Function description24
3.1Function description of the temperature control unit24
3.1.1General functions24
3.2Information on the thermal fluids24
3.3To be noted when planning the test25
4Setup mode26
4.1Setup mode26
4.1.1Turning on the temperature control unit26
4.1.2Turning off the temperature control unit26
4.2Filling, venting and draining26
4.2.1Externally closed application27
4.2.1.1Filling and venting externally closed application27
4.2.1.2Draining externally closed applications28
5Normal operation29
5.1Automatic operation29
5.1.1Temperature control29
5.1.1.1Starting the temperature control process29
5.1.1.2Ending the temperature control process29
6Service/maintenance30
6.1Electrical fuse30
6.2Maintenance30
6.2.1Function check and visual inspection30
6.2.2Replacing temperature control hoses31
6.2.3Clean liquefier fins (air-cooled temperature control unit)31
6.3Thermal fluid inspection, replacement and circuit cleaning32
6.3.1Thermal fluid inspection32
6.3.2Thermal fluid replacement33
6.3.2.1Externally closed application33
6.3.3Rinsing the thermal fluid circuit33
6.4Cleaning the surfaces34
6.5Inspect the mechanical seal35
6.6Plug contacts35
6.7Decontamination/repairs35
7Shutting down36
7.1Safety instructions and basic principles36
7.2Switch-off36
7.3Draining the temperature control unit37
7.4Uninstalling an external application37
7.5Packing37
7.6Shipping37

На странице напечатано оглавление (содержание), а не матрица конфигураций; данные приведены как в тексте.

Identification / symbols in the operation manual

Identification / symbolDescription
→Reference to information / procedure.
»TEXT«Reference to a chapter in the operation manual. In the digital version, the text is clickable.
>TEXT< [NUMBER]Reference to the wiring diagram in the annex. The designation and the search digit are specified.
>TEXT< [LETTER]Reference to a drawing in the same paragraph. The designation and the search digit are specified.
▪List, first level
‒List, second level

Proper disposal of resources and consumables

Material / AidsDisposal / Cleaning
Packaging materialKeep the packaging material for future use (e.g. transport).
Thermal fluidPlease refer to the safety data sheet of the thermal fluid used for information on its proper disposal. Use the original thermal fluid container when disposing it.
Filling accessories, e.g. beakerClean the filling accessories for reuse. Make sure that the materials and cleaning agents used are properly disposed of.
Aids such as towels, cleaning clothsTools used to take up spilled thermal fluid must be disposed of in the same fashion as the thermal fluid itself. Tools used for cleaning must be disposed of depending on the cleaning agent used.
Cleaning agents such as stainless steel cleaning agents, sensitive-fabrics detergentsPlease refer to the safety data sheet of the cleaning agent used for information on its proper disposal. Use the original containers when disposing of large quantities of cleaning agents.
Consumables such as air filter mats, temperature control hosesPlease refer to the safety data sheet of the consumables used for information on their proper disposal.

Rating of laboratory thermostats and laboratory baths

ClassificationTemperature control mediumTechnical requirementsIdentification d)
INon-combustible a)Overheat protection c)NFL
IICombustible b)Adjustable overheat protectionFL
IIICombustible b)Adjustable overtemperature protection and additional low-level protectionFL

a) Usually water; other fluids only if non-combustible even within the temperature range of an individual fault. b) The temperature control media must have a fire point of ≥ 65 °C. c) The overheat protection can, for instance, be realized using a suitable fill level sensor or a suitable temperature limiter. d) Optional at the choice of the manufacturer.

Wrench sizes and torques

ConnectionSleeve nut wrench sizeConnector wrench sizeRecommended torques in NmMaximum torques in Nm
M16x119172024
M24x1.527274756
M30x1.536327993
36367993
M38x1.54646130153
G-thread (flat-sealing)Adapt the torque to the material of the flat seal used. First hand-tighten the temperature control hose. When using adapters, do not overtighten the G-thread on the pump connection when connecting a temperature control hose. When connecting a temperature control hose to the adapter piece, secure the G thread against overwinding.

Строка для G-thread (flat-sealing) содержит объединённую ячейку с текстом-пояснением, занимающую остальные столбцы.

Function check and visual inspection

Cooling*DescriptionMaintenance intervalCommentPerson responsible
A/WVisually inspect hoses and hose connectionsPrior to switching on the temperature control unitExchange leaking hoses and hose connections prior to switching on the temperature control unit. → Page 31, section »Replacing temperature control hoses«.Operating company and / or operators
A/WCheck the power supply cablePrior to switching on the temperature control unit or on relocationDo not start the temperature control unit if the power supply cable is damaged.Qualified electrician (BGV A3)
AClean the perforated sheetAs requiredClean the perforated sheet of the temperature control unit with a damp clothOperating company
A/WThermal fluid inspectionAs required–Operating company and / or operators
A/WCheck the mechanical sealsMonthly→ Page 35, section »Inspect the mechanical seal«.Operating company and / or operators
ACheck the liquefier finsAs required, after 3 months at the latest→ Page 31, section »Clean liquefier fins (air-cooled temperature control unit)«.Operating company and / or operators
A/WCheck the temperature control unit for damage and stabilityEvery 12 months or after a change of location–Operating company and / or operators

* Cooling

Cooling*

DescriptionMaintenance intervalCommentPerson responsible
Exchange safety-relevant electric and electromechanical components20 yearsHave the exchange only carried out by certified personnel (such as Huber service engineers). Please contact Customer Support. → Page 38, section »Contact data«Operating company

*A = Air cooling; W = Water cooling; U = Applicable only for Unistats

Engineering Facts

13 facts · every claim linked to a page
Safety

The unit must never be installed or started inside an ATEX zone because it is not explosion-protected without an Ex px cabinet.

Determines whether the unit can be placed in a hazardous area at all.

Source
“Do NOT install or start up the temperature control unit within an ATEX zone.”
Installation

A condensation water / thermal fluid drip tray must be installed below the unit by the responsible body.

Affects site preparation and civil works before commissioning.

Source
“The responsible body must install a condensation water / thermal fluid drip tray below the temperature control unit.”
Installation

Minimum 20 cm clearance is required on left, right, front and rear sides for air-cooled units.

Insufficient clearance causes overheating and reduced cooling capacity.

Source
“Maintain wall and ceiling clearance for adequate air exchange”
Installation

The unit must be allowed to acclimate about 2 hours when moving between cold and warm environments before power-on.

Prevents condensation-induced electrical damage at first start-up.

Source
“Allow the temperature control unit to acclimate for about 2 hours when changing from a cold to a warm environment (or vice versa). Do not turn on the temperature control unit before!”
Installation

Maximum torque values for pump connections must not be exceeded and a leak test must always be performed.

Over-torquing damages fittings; under-torquing causes leaks.

Source
“The values of the maximum torque (see table) must not be exceeded.”
Installation

The circulation flow must connect to the lower port of the application and the return to the higher port to allow venting.

Wrong orientation traps air and prevents proper venting.

Source
“you must ensure that the >Circulation flow< [1] connection from the temperature control unit is attached to the lower connection point of the application and the >Circulation return< [2] into the temperature control unit is attached to the higher connection point of the application.”
Installation

The power cable must not exceed 3 m so the unit can be disconnected from mains at any time.

Affects electrical layout and safety disconnection capability.

Source
“Do not use a power cable that is longer than 3 m to be able to disconnect the temperature control unit at any time from the mains.”
Selection

Flammable thermal fluids must not be used in this unit.

Restricts fluid selection to non-flammable media only.

Source
“Flammable thermofluids must not be used in the temperature control unit!”
Selection

Thermal fluid viscosity must not exceed 50 mm²/s at the lowest working temperature and density must not exceed 1 kg/dm³.

Defines fluid compatibility limits for pump and heat transfer performance.

Source
“The maximum viscosity of the thermal fluid must not exceed 50 mm²/s at the lowest working temperature!”
Selection

Water without ethylene glycol is used at ≥ +3 °C; water-ethylene glycol mixture is required below +3 °C.

Determines which fluid to specify based on the target operating temperature.

Source
“Thermal fluid: Water-ethylene glycol mixture”
Operation

The thermal fluid circuit must not be closed by shut-off valves during active circulation.

Prevents pump damage from dead-heading.

Source
“Do not close the thermal fluid circuit during an active circulation by means of shut-off valves.”
Operation

The unit must be filled to about 1 cm below the hose end of the level indicator and drain.

Correct fill level ensures expansion volume and prevents overflow.

Source
“Fill the temperature control unit up to 1 cm below the hose end of the >Level indicator and drain< [38].”
Operation

Before draining, the thermal fluid must be at room temperature (20 °C).

Prevents burns/frostbite and ensures drainability.

Source
“Before draining, ensure that the thermal fluid has room temperature (20 °C).”